| Plan Review Notes For Permit 22040490 |
| Permit Number |
22040490 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-20 12:51:28 | PER CITY CODES, ALL WORK IS SUBJECT TO FIELD | | | INSPECTIONS AND APPROVAL. | | | | | | THE PROPOSED LOCATIONS OF THE FIRE HYDRANT AND FDC ARE | | | ACCEPTABLE WITH ANY CHANGES CLOSELY COORDINATED WITH | | | THE DIVISION OF FIRE PREVENTION. | | | | | | 1) INSTALL, TEST AND INSPECT PER NFPA? 24 STANDARD FOR | | | THE INSTALLATION OF PRIVATE FIRE SERVICE MAINS AND | | | THEIR APPURTENANCES, 2013 EDITION | | | PLEASE ENSURE COMPLIANCE. | | | 2) DO NOT COVER OVER ANY JOINTS PRIOR TO INSPECTION. | | | PLEASE ENSURE COMPLIANCE | | | | | | LT. BRIAN DOLAN | | | DIVISION OF FIRE PREVENTION | | | 561-804-4752 | | | [email protected] |
|