| Plan Review Notes For Permit 22040477 |
| Permit Number |
22040477 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-18 08:06:55 | 1ST REVIEW FBC-2020 RES. PLUMBING | | | PERMIT- 22040477 | | | 4/18/22 | | | | | | CODES IN EFFECT: | | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | | 2020 | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) PLEASE PROVIDE A BACKFLOW SUBMITTAL THAT DOES NOT | | | BEAR THE CITY APPROVAL STAMP AND PERMIT NUMBER FROM A | | | PREVIOUS PROJECT. BACKFLOW PREVENTERS ARE PRIMARY | | | PERMITS AND ARE SUBMITTED SEPARATED- SEC. 105.1 & | | | 107.2.1 WPB. | | | | | | 2) PROVIDE A BASIC SITE PLAN SHOWING THE LOCATION OF | | | THE BACKFLOW PREVENTER- SEC. 107.2.1 WPB. | | | | | | 3) THE $500.00 VALUE APPEARS LOW FOR THE COSTS OF THE | | | BACKFLOW PREVENTER AND THE INSTALLATION- TOTAL COST | | | SHALL INCLUDE LABOR, MATERIALS, AND EQUIPMENT- SEC. | | | 109.3 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | | | | |
|