| 2022-09-06 09:34:07 | PLAN REVIEW COMMENTS | | | | | | 3RD REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SUBMIT COPIES OF THE ACTUAL TEST REPORTS FOR THE | | | FLAME SPREAD AND SMOKE DEVELOPED FOR THE GENIEMAT | | | FLOORING SOUND INSULATION. I HAVE NO RECORD ON FILE OF | | | THE ACTUAL FLAME SPREAD TEST REPORT FOR THIS PRODUCT. | | | FBC 603.1 FLAME SPREAD - ASTM E 84-09 | | | | | | | | | |
|