2022-06-03 12:17:3522040424 200 ARKONA CT.
  
 COMMENT 1: RESPONSE TO ASTM E-84 IS DENIED. LETTER IS
 DENIED AS IT DOES NOT ADDRESS FBC 603.1. THE LETTER IS
 SPECIFIC TO FBC 804.
  
 THE PROPOSED FLOOR FINISH AS STATED IN THE ICC LETTER
 REFERENCED IN COMMENT 1 IS VINYL. AIRBORNE AND
 STRUCTURE BORE SOUND TEST RESULTS RESPONSES DO NOT
 SPECIFICALLY ADDRESS VINYL FLOOR FINISH. ALSO THE
 REPORT STATES IT DOES NOT CONSTITUTE CERTIFICATION OF
 THIS PRODUCT ETC. YOU WILL NEED TO PROVIDE A SIGNED AND
 SEALED LETTER FROM A DESIGN PROFESSIONAL ALONG WITH THE
 REPORT STATING WHETHER OR NOT TEST RESULTS MEET FBC
 1207.2 AND 1207.3.
  
 JIM BAKER
 561-805-6710
 [email protected]
  
 PREFERRED METHOD OF COMMUNICATION IS EMAIL
  
 A COMMENT/RESPONSE LETTER WILL PROVIDE A MORE
 EXPEDITIOUS REVIEW.
  