| 2023-05-09 10:22:58 | FAILED |
| | |
| | 1) THE COMMENTS LISTED BELOW MUST BE CORRECTED NOT ONLY |
| | ON THE BUILDING PERMIT, BUT ALSO AS PART OF THE MINOR |
| | PLANNED DEVELOPMENT AMENDMENT THAT HAS BEEN SUBMITTED |
| | TO THE PLANNING DIVISION. |
| | |
| | 2) THERE IS A DISCREPANCY BETWEEN WHAT IS SHOWN ON THE |
| | DIMENSION SITE PLAN AND THE SURVEY. THE SURVEY SHOWS A |
| | TOTAL OF 60 FEET BETWEEN THE EXTERIOR PARKING GARAGE |
| | WALL COLUMNS AND THE INTERIOR GARAGE COLUMNS. THE |
| | 60-FOOT WIDTH IS THE MINIMUM NECESSARY TO PROVIDE TWO |
| | 18-FOOT DEEP PARKING STALLS AND THE 24-FOOT WIDE DRIVE |
| | AISLE MEETING CODE REQUIREMENTS. THE DIMENSION SITE |
| | PLAN SHOWS THE NEW EV CHARGING UNITS AND SIGNS LOCATED |
| | APPROXIMATELY 1-FOOT INSIDE OF THE EXTERIOR WALL, |
| | RESULTING IN THERE BEING EITHER INSUFFICIENT DEPTH OF |
| | THE EV SPACES OR A REDUCTION IN THE REQUIRED DRIVE |
| | AISLE WIDTH. PROVIDE A FULL DIMENSIONED CROSS SECTION |
| | FROM THE EXTERIOR TO THE CENTER OF THE GARAGE SHOWING |
| | ACCURATE DIMENSIONS FOR THE SPACES ON BOTH SIDES OF THE |
| | DRIVE AISLE AND THE DRIVE AISLE THAT MEET CODE. PROVIDE |
| | A DIMENSIONED DRAWING OF THE EV CHARGING UNIT THAT |
| | INCLUDES THE DEPTH OF THE UNIT IN PLAN AND ELEVATION. |
| | THE EV CHARGING UNIT DIMENSION AND SIGN LOCATION SHALL |
| | BE ACCURATELY SHOWN ON THE DIMENSIONED SITE PLAN. NOTE: |
| | IT APPEARS THAT THE DEPTH OF THE EV CHARGING UNIT AND |
| | SIGN IS LESS THAN THE DEPTH OF THE EXTERIOR COLUMN, SO |
| | THE FACE OF THE UNIT AND THE SIGN COULD BE MOVED |
| | BETWEEN THE COLUMNS AND STILL MEET THE MINIMUM DEPTH |
| | ACROSS THE PARKING GARAGE. |
| | |
| | 3) SHOW THE FULL ACCESSIBLE ROUTE FROM THE ACCESS AISLE |
| | TO THE EXIT FROM THE GARAGE. PLEASE NOTE THAT THE ROUTE |
| | IS NOT PERMITTED TO DIRECT THE ADA USER BEHIND A PARKED |
| | VEHICLE THAT IS NOT THEIR OWN. |
| | |
| | CONTACT ERIC SCHNEIDER @ 561-822-1446 |
| | [email protected] |