| 2022-04-27 07:56:13 | 1ST REVIEW FBC-2020 RES. PLUMBING |
| | PERMIT- 22040406 |
| | 4/27/2022 |
| | |
| | CODES IN EFFECT: |
| | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION |
| | 2020 |
| | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION |
| | 2020 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) THE $1500 PERMIT VALUE IS A LOW VALUE FOR THE SCOPE |
| | OF WORK FOR THE POOL PROJECT. PROVIDE AN ITEMIZED COST |
| | BREAKDOWN THAT INCLUDES LABOR, MATERIALS, POOL |
| | EQUIPMENT, SITE WORK, AND DESIGN FEES- SEC. 109.3 WPB. |
| | |
| | 2) SHEET 3: PROVIDE THE POOL TURNOVER RATE- SEC. |
| | R4501.6.6 FBC RES. |
| | |
| | 3) SHEET 3: SUBMIT TOTAL DYNAMIC HEAD (TDH) |
| | CALCULATIONS FOR THE MAXIMUM SYSTEM FLOW. THE MAXIMUM |
| | FLOW OF THE PUMP FROM ITS PUMP CURVE AND THE SIMPLIFIED |
| | TOTAL DYNAMIC HEAD CALCULATION IS NO LONGER ALLOWED TO |
| | BE USED IN DETERMINING MAXIMUM SYSTEM FLOW RATE PER |
| | ANSI/APSP/ICC 7- 2013 SECS. 4.4.9, 4.4.9.1. THE 2013 |
| | EDITION ADDRESSES FLOW RATE IN GALLONS PER MINUTE |
| | (GPM). IT REQUIRES THAT MAXIMUM SYSTEM FLOW RATE DOES |
| | NOT EXCEED THE LISTED MAXIMUM FLOW RATE OF THE SUCTION |
| | OUTLET FITTING ASSEMBLY (DRAIN COVER). THE TDH |
| | CALCULATIONS MUST INCLUDE ALL OF THE SYSTEM COMPONENTS |
| | INCLUDING SUCTION AND RETURN PIPING, FITTINGS, VALVES, |
| | HEATER, FILTER, AND CHLORINATOR. ALL SYSTEM COMPONENTS |
| | EXCEPT THE PUMP. |
| | |
| | 4) SHEET 2: SUBMIT SPECS FOR THE REPLACED MAIN DRAIN |
| | ASSEMBLY- SEC. R4501.6.6 FBC RES. |
| | |
| | 5) SHEET 3 SPECIFICATIONS: UPDATE CONFORMANCE STANDARDS |
| | IN NOTE 1 IN ACCORDANCE WITH SEC. R4501.6.1 FBC RES. |
| | |
| | 6) SHEET 3: PLEASE PLACE A NOTE TO INDICATE A SEPARATE |
| | PERMIT IS REQUIRED FOR INSTALLATION OF THE GAS POOL |
| | HEATER- SECS. 105.1 & 107.1 WPB. |
| | |
| | 7) SHEET 3: PLACE A NOTE TO INDICATE THERE IS AN |
| | EXISTING BACKFLOW PREVENTER FOR THE POTABLE WATER |
| | SERVICE OR A FL. LICENSED PLUMBING CONTRACTOR SHALL |
| | OBTAIN A SEPARATE PERMIT FOR INSTALLATION OF THE |
| | BACKFLOW PREVENTER IN ACCORDANCE WITH SECTION 105.1 WPB |
| | AND SEC. 90-33 WPB CODE OF ORDINANCES. THE DEVICE SHALL |
| | BE TESTED AND CERTIFIED BY THE WPB UTILITIES DEPARTMENT |
| | PRIOR TO FINAL INSPECTION BY THE BUILDING DEPARTMENT. |
| | PLEASE CONTACT THE WPB UTILITIES CENTRAL OPERATIONS |
| | DEPT.AT 561-822-2210 FOR FURTHER INFORMATION. A |
| | BACKFLOW PREVENTER SHALL ALSO BE INSTALLED AT THE |
| | AUTOFILL IF INSTALLED. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. |