| Plan Review Notes For Permit 22040404 |
| Permit Number |
22040404 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-06-09 10:22:36 | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1/0 CONDUCTORS FOR SERVICE DOES NOT APPEAR TO BE LARGE | | | ENOUGH. LOAD CALCULATION SUBMITTED IS NOT DONE IN | | | ACCORADANCE WITH ARTICLE 220 OF THE NEC. | | | | | | | | | PLEASE SUBMIT A LOAD CALCULATION THAT IS DONE PER | | | ARTICLE 220. |
|