| 2022-04-25 15:20:14 | 1ST PLUMBING REVIEW |
| | |
| | V7 FPC - 2020 FLORIDA PLUMBING CODE |
| | V7 FGC - 2020 FLORIDA FUEL GAS |
| | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE |
| | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE |
| | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE |
| | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION |
| | 2021 F.S. - 2021 FLORIDA STATUTES |
| | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE |
| | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE |
| | FBC CHAPTER 1 |
| | |
| | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED |
| | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. |
| | |
| | THIS REVIEW WAS FOR THE MAIN HOUSE ONLY. THE CARRIAGE |
| | HOUSE WILL BE A SEPERATE REVIEW ON A SEPERATE PERMIT. |
| | |
| | 1. PAGE P-1 MAIN HOUSE - 2020 FRC P3108.1 - THE TWO |
| | WATER CLOSETS ARE NOT VENTED. EACH FIXTURE DRAIN SHALL |
| | CONNECT HORIZONTALLY TO THE HORIZONTAL BRANCH BEING WET |
| | VENTED OR SHALL HAVE A DRY VENT. THE FIXTURE DRAIN OF |
| | THESE TWO WATER CLOSETS SHOULD BE CONNECTED TO THE WET |
| | VENTED BRANCH NEAR IT TO BE IN COMPLIANCE. |
| | |
| | 2. PAGE P-2 MAIN HOUSE - 2020 FRC P2903.7 - THE SIZE OF |
| | THE WATER LINES AT THE INLET AND OUTLET OF THE TANKLESS |
| | WATER HEATER DO NOT COMPLY WITH THE MINIMUM SIZE OF THE |
| | BRANCH MAINS. PLEASE INDICATE HOW THE 1/2" WATER PIPES |
| | ON THE WATER HEATER WILL SUPPLY 3/4" MAINS. ALSO, |
| | PLEASE INDICATE THE MAX FLOW OF WATER THROUGH THE WATER |
| | HEATER AND SHOW HOW IT WILL SUPPLY ALL THE HOT WATER |
| | OUTLETS IN THE HOUSE DURING PEAK DEMAND. |
| | |
| | 3. PAGE P-2 MAIN HOUSE - 2020 FRC P2903.6 - SHOW YOUR |
| | HOT WATER FIXTURE UNITS AND SHOW HOW THE 4.8 GPM WILL |
| | MEET THE PEAK DEMAND OF HOT WATER PER TABLE 2903.6. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |
| | |