Plan Review Notes
Plan Review Notes For Permit 22040370
Permit Number 22040370
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-03 12:26:44 
 WEST PALM BEACH DEVELOPMENT SERVICES-CONSTRUCTION
 SERVICES/ BUILDING DIVISION
 2020 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 22040370
 ADD: 3800 WASHINGTON RD. # 607
 CONT: WINDOWMAN OF SOUTH FLORIDA
 TEL: 943-946-1553
 E-MAIL:
  
 2020 FLORIDA BUILDING CODE W 2020 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 2020 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: TUES. MAY 3RD/ 2022
 ACTION: DENIED
  
 1) THE ENGINEERING EXPRESS SHEET LIST A C EXPOSURE WITH
 ASSOCIATED PRESSURES. THE EXPOSURE CATEGORY CAN NOT BE
 DETERMINED AT THIS TIME, THE LOCATION OF THIS UNIT WILL
 NEED TO BE SHOWN IN THE OVERALL FOOTPRINT OF THE
 BUILDING TO SEE IF THE EXPOSURE IS A C OR D EXPOSURE.
 2020 FBC-BUILDING 1609.4.3. EXPOSURE CATEGORIES,
 EXPOSURE D.
 EXPOSURE D SHALL APPLY WHERE THE GROUND SURFACE
 ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, PREVAILS
 IN THE UPWARD DIRECTION FOR A DISTANCE OF AT LEAST
 5,000 FEET OR 20 TIMES THE HEIGHT OF THE BUILDING,
 WHICHEVER IS GREATER. EXPOSURE SHALL ALSO APPLY WHERE
 THE GROUND SURFACE ROUGHNESS IMMEDIATELY UPWIND OF THE
 SITE IS B OR C , AND THE SITE IS WITHIN A DISTANCE OF
 600 FEET OR 20 TIMES THE BUILDING HEIGHT, WHICHEVER IS
 GREATER, FROM AN EXPOSURE D CONDITION AS DEFINED IN THE
 PREVIOUS SENTENCE.
  
 2) THE SLIDING GLASS DOOR REPORT FL-22267-R9 PLEASE
 IDENTIFY IN THE PRODUCT APPROVAL BEFORE SUBMITTING TO
 THE BUILDING DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING,
 PLEASE IDENTIFY THE OPENING WIDTH & HEIGHT, SILL
 HEIGTH, TYPE OF GLAZING, MULLION SIZE, LENGTH IF
 UNREINFORCED OR REINFORCED INFORMATION IF REQUIRED,
 ATTACHMENTS AND ASSOCIATE PRESSURES FOR EACH OPENING
 SIZE. 2020 FBC-B 1405.13.1 INSTALLATION. WINDOWS AND
 DOORS SHALL BE INSTALLED IN ACCORDANCE WITH APPROVED
 MANUFACTURER?S INSTRUCTIONS. FASTENER SIZE AND SPACING
 SHALL BE PROVIDED IN SUCH INSTRUCTIONS AND SHALL BE
 CALCULATED BASED ON MAXIMUM LOADS AND SPACING USED IN
 THE TESTS.
  
 3) A TRANSMITTAL LETTER / NARRATIVE LISTING THE
 ORIGINAL REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF
 THE REVISION MADE, IDENTIFYING THE SHEET OR
 SPECIFICATION PAGE WHERE THE CHANGES CAN BE FOUND WILL
 HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 PLEASE NOTE WITH THE LACK OF INFORMATION FOR THIS
 REVIEW, SUBSEQUENT REMARKS MAYBE MADE IN THE NEXT
 REVIEW CYCLE.
 MY WORK HOURS ARE USUALLY TUES. & WED. 7:30 AM- 4:30 PM
 PART-TIME/ SEMI-RETIRED.
 IF YOU WISH TO SPEAK WITH A PLANS EXAMINER BEFORE I GET
 BACK INTO THE OFFICE CALL
 (561)805-6700 AND ASK FOR THE PLANS EXAMINER ON-CALL.
 THANK YOU.
  
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  