| Plan Review Notes For Permit 22040360 |
| Permit Number |
22040360 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-04 11:00:14 | FIRE COMMENTS: | | | (1) PROVIDE A SITE PLAN FOR VERIFICATION OF THE | | | GENERATOR LOCATION. NFPA 1, 1.14, NFPA 110 7.1.1 | | | (2) PROVIDE MOUNTING DETAILS. NFPA 110 7.4 | | | C. WALKER, SENIOR FIRE INSPECTOR | | | 561-804-4762 | | | [email protected] | | | |
|