Plan Review Notes
Plan Review Notes For Permit 22040356
Permit Number 22040356
Review Stop P
Sequence Number 1
Notes
Date Text
2022-04-21 14:37:541ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMEND 107.2.1 ? PLEASE CLARIFY FOR CODE
 COMPLIANCE.
 PAGE P-1 ? DETAIL D ? THE POWDER BATH RISER HAS THE
 LAVATORY FIXTURE DRAIN CONNECTED TO THE SANITARY DRAIN
 STACK WITHOUT A VENT.
 PAGE P-1 ? DETAIL B ? THE LAUNDRY RISER APPEARS TO BE
 CONNECTING TO A WASTE STACK, HOWEVER, THE STACK THAT
 WAS UTILIZED BY THE POWDER BATH WAS NOT LIKELY A WASTE
 STACK SINCE WASTE STACKS ARE NOT TO RECEIVE THE
 DISCHARGE OF WATER CLOSETS.
 FOR ALL THE RISERS AND STACKS, PLEASE SHOW WHAT EXISTS
 IN THE BUILDING AS WASTE STACKS AND WHAT IS SANITARY
 DRAINAGE STACKS. PLEASE SHOW THE DETAILS OF THE STACKS
 TO DETERMINE WHETHER THEY ARE DRAINAGE STACKS, WASTE
 STACKS, OR SINGLE STACK SYSTEMS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  