2022-04-20 13:56:14THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THERE ARE INDICATIONS OF FIRE SPRINKLER PROTECTION
 WITHIN THE ELEVATOR MACHINE ROOM.
  
 PER NFPA 13:
  
 8.15.5.3 AUTOMATIC FIRE SPRINKLERS SHALL NOT BE
 REQUIRED IN ELEVATOR MACHINE ROOMS, ELEVATOR
 MACHINERY SPACES, CONTROL SPACES, OR HOISTWAYS OF
 TRACTION ELEVATORS INSTALLED IN ACCORDANCE
 WITH THE APPLICABLE PROVISIONS IN NFPA 101, OR THE
 APPLICABLE BUILDING CODE, WHERE ALL OF THE
 FOLLOWING CONDITIONS ARE MET:
 (1) THE ELEVATOR MACHINE ROOM, MACHINERY SPACE, CONTROL
 ROOM, CONTROL SPACE, OR HOISTWAY OF
 TRACTION ELEVATOR IS DEDICATED TO ELEVATOR EQUIPMENT
 ONLY.
 (2) THE ELEVATOR MACHINE ROOM, MACHINE ROOM, MACHINERY
 SPACE, CONTROL ROOM, CONTROL
 SPACE, OR HOISTWAY OF TRACTION ELEVATORS ARE PROTECTED
 BY SMOKE DETECTORS, OR OTHER AUTO MATIC FIRE DETECTION,
 INSTALLED IN ACCORDANCE WITH NFPA 72.
 (3) THE ELEVATOR MACHINERY SPACE, CONTROL ROOM, CONTROL
 SPACE, OR HOISTWAY OF TRACTION ELEVA TORS IS SEPARATED
 FROM THE REMAINDER OF THE BUILDING BY WALLS AND
 FLOOR/CEILING OR ROOF/
 CEILING ASSEMBLIES HAVING A FIRE RESISTANCE RATING OF
 NOT LESS THAN THAT SPECIFIED BY THE
 APPLICABLE BUILDING CODE.
 (4) NO MATERIALS UNRELATED TO ELEVATOR EQUIPMENT ARE
 PERMITTED TO BE STORED IN ELEVATOR
 MACHINE ROOMS, MACHINERY SPACES, CONTROL ROOMS, CONTROL
 SPACES, OR HOISTWAYS OF TRAC TION ELEVATORS.
 (5) THE ELEVATOR MACHINERY IS NOT OF THE HYDRAULIC
 TYPE.
  
 PLEASE REVIEW AND CONFIRM AND OR CORRECT.
  
  
 2) AS THIS IS AN OLDER BUILDING WITH POSSIBLY OLDER
 ELEVATOR CONSTRUCTION, AND THERE ARE NO SPRINKLER AT
 THE TOP OF THE SHAFT, PER NFPA 13:
  
 8.15.5.5* UPRIGHT, PENDENT, OR SIDEWALL SPRAY
 SPRINKLERS SHALL BE INSTALLED AT THE TOP OF ELEVATOR
 HOISTWAYS.
  
 8.15.5.6 THE SPRINKLER REQUIRED AT THE TOP OF THE
 ELEVATOR HOISTWAY BY 8.15.5.5 SHALL NOT BE
 REQUIRED WHERE THE HOISTWAY FOR PASSENGER ELEVATORS IS
 NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE
 AND THE CAR ENCLOSURE MATERIALS MEET THE REQUIREMENTS
 OF ASME A17.1, SAFETY CODE FOR ELEVATORS AND ESCALATORS
  
 PLEASE REVIEW AND CONFIRM AND OR CORRECT.
  
  
  
 3) SHEET FS 5 - THERE IS AN INDICATION WITHIN THE
 LEGEND OF PRV, HOWEVER, THERE ARE NO INDICATIONS ON THE
 STANDPIPE RISER(EXISTING OR NEW) OF ANY APPLICBALE
 PRV'S ON THE APPLICABLE FLOORS.
  
 PLEASE REVIEW AND PROVIDE DETAILS.
  
  
  
 4) THERE IS AN EXISTING ELECTRIC FIRE PUMP INDICATED,
 PLEASE CONFIRM THAT THIS ELECRTIC PUMP IS CONNECTED TO
 THE GENERATOR AND/OR IT IS NOT REQUIRED TO BE CONNECTED
 DUE THE HYDRALIC CALCULATIONS SND NOT NEEDING IT.
  
  
 5) SHEET FS 1 - THERE DOES NOT APPEAR AN INDICATION OF
 A SIDEWALL SPRINKLER HEAD AT THE BASE OF THE ELEVATOR
 SHAFT.
  
 PER NFPA 13:
  
 8.15.5.1* SIDEWALL SPRAY SPRINKLERS SHALL BE INSTALLED
 AT THE BOTTOM OF EACH ELEVATOR HOISTWAY
 NOT MORE THAN 2 FT (600 MM) ABOVE THE FLOOR OF THE PIT
  
 8.15.5.2 THE SPRINKLER REQUIRED AT THE BOTTOM OF THE
 ELEVATOR HOISTWAY BY 8.15.5.1 SHALL NOT BE
 REQUIRED FOR ENCLOSED, NONCOMBUSTIBLE ELEVATOR SHAFTS
 THAT DO NOT CONTAIN COMBUSTIBLE HYDRAU LIC FLUIDS
  
 PLEASE REVIEW AND CORRECT OF PROVIDE DEAILS OF
 COMPLIANCE.
  
  
 6) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 7) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
 PETER LEDUC
 FIRE MARSHAL