Plan Review Notes
Plan Review Notes For Permit 22040335
Permit Number 22040335
Review Stop I
Sequence Number 4
Notes
Date Text
2022-06-07 07:13:33THIS REVIEW WAS ADDED TO PROVIDE FURTHER CLARIFICATION
 FOR THE PRIVATE PROVIDER PLAN REVIEW.
  
 22030685 (MASTER) - SHEET IA-310 PREPARED BY DIEGO
 ROBERTO MARTINEZ ([email protected]), AR99036. THE
 PLAN SUBMITTED IS DATED 11/23/21.
  
 THE PAGE SUBMITTED FOR 22040335 HAS A DIFFERENT DATE,
 CLIENT REVISIONS 12/7/2021, IS OF POOR QUALITY (APPEARS
 TO BE A SCAN), AND IS NOT DIGITALLY SIGNED. BECAUSE THE
 PAGE SUBMITTED IS A SCAN RATHER THAN A PDF FROM THE
 ARCHITECT'S OFFICE, WE CANNOT EASILY DETERMINE CTHE
 CHANGS TO SEE IF A REVISION SHOULD BE REQUIRED.
  
 TWO PAGES WERE UPLOADED, ONE WAS THE POOR QUALITY
 REVISED PLAN, THE SECOND PAGE IS THE SAME PAGE FROM THE
 ISSUED PERMIT, VERSION 11/23/21. IT IS NOT CLEAR WHY
 THAT WAS SUBMITTED, PLEASE EMAIL
 [email protected] AND REQUEST THAT IT BE REMOVED.
  
 THE AFFIDAVIT IS NOT CORRECT FOR THE PAGE SUBMITTED,
 REFERS TO WRONG VERSION.
  
 IT APPEARS THAT A REVISION IS REQUIRED.
  
 THE AFFIDAVIT FOR THE MASTER WAS EVALUATED ONLY FOR
 CONSISTENCY BETWEEN THE AFFIDAVIT AND THE PLANS
 SUBMITTED. HOWEVER IN REEVALUATION, IT IS NOT CLEAR WHY
 AN ELECTRICAL PAGE WOULD APPEAR ON THE BUILDING
 REVIEWER'S AFFIDAVIT. SHEET IA-310 IS LOW VOLTAGE AND
 ELECTRICAL, NOT WITHIN THE SCOPE OF A BUILDING PLANS
 EXAMINER LICENSE.
  