| Plan Review Notes For Permit 22040327 |
| Permit Number |
22040327 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-03 17:22:24 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) ARC FAULT CIRCUITS ARE REQUIRED BY SECTION 210.12(C) | | | | | | 2) LIGHTING CONTROL IN ROOMS IS REQUIRED BY C405.2 | | | | | | 3) PLEASE PROVIDE A COST BREAK DOWN FOR WORK (25K) | | | | | | 4) PLEASE PROVIDE RISER DIAGRAM SHOWING ALL NEW | | | EQUIPMENT TO BE INSTALLED. 215.5 | | | | | | 5) SIGNATURE SHOWS AS A FAIL BUT IT IS OK WILL FIX ON | | | NEXT REVIEW. |
|