Plan Review Notes
Plan Review Notes For Permit 22040327
Permit Number 22040327
Review Stop E
Sequence Number 1
Notes
Date Text
2022-05-03 17:22:24ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) ARC FAULT CIRCUITS ARE REQUIRED BY SECTION 210.12(C)
  
 2) LIGHTING CONTROL IN ROOMS IS REQUIRED BY C405.2
  
 3) PLEASE PROVIDE A COST BREAK DOWN FOR WORK (25K)
  
 4) PLEASE PROVIDE RISER DIAGRAM SHOWING ALL NEW
 EQUIPMENT TO BE INSTALLED. 215.5
  
 5) SIGNATURE SHOWS AS A FAIL BUT IT IS OK WILL FIX ON
 NEXT REVIEW.