| Plan Review Notes For Permit 22040290 |
| Permit Number |
22040290 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-09-16 11:03:47 | SFR ADDITION - REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) THERE ARE MULTIPLE ROOFING SYSTEMS IN THE ROOFING | | | PRODUCT APPROVAL - - PRODUCT APPROVAL (18-0919.07) FOR | | | THE FLAT DECK ROOFING = NEED TO CHOOSE A ROOFING SYSTEM | | | IN THE PRODUCT APPROVAL THAT MEETS THE REQUIRED WIND | | | DESIGN PRESSURE - PLEASE CIRCLE THE ROOFING SYSTEM TO | | | BE USED IN THE PRODUCT APPROVAL - IF NEEDED PLEASE | | | PROVIDE ADDITIONAL ATTACHMENT DETAILS FROM AN ARCHITECT | | | OR ENGINEER FOR THE ROOF ZONES 2 AND 3 WHICH MAY | | | REQUIRE A HIGHER WIND PRESSURE THEN THE CHOSEN ROOFING | | | SYSTEM - SEE GENERAL LIMITATION NOTE 7 ON THE PRODUCT | | | APPROVAL. | | | | | | | | | | | | | | | |
|