| 2022-06-10 10:32:08 | ELECTRIC REVIEW FAILED |
| | 1) SMOKE ALARMS ARE NOT DETAILED IN AND OUTSIDE OF |
| | BEDROOM 4 AS PER FBC R314.3 |
| | 2) PLEASE DETAIL THE REQUIRE OUTDOOR RECEPTACLE AT |
| | MASTER BEDROOM EXIT AS PER NEC 210.52(E)(3) BALCONIES, |
| | DECKS, AND PORCHES |
| | 3) PLANS DETAIL A NEW LOCATION FOR METER AND PANEL. |
| | RISER DETAILS AN EXISTING METER MAIN AND EXISTING |
| | PANEL. FLOOR PLANS DO NOT DETAIL A SYMBOL FOR THE 200 |
| | AMP PANEL. PLEASE CORRECT NOMENCLATURE FOR METER ON |
| | RISER AS NEW AND DETAIL 200 AMP ELECTRIC PANEL |
| | LOCATION. NEC 215.5 AND FBC 107.2 |
| | 4) LOAD CALCULATION APPEARS TO HAVE INCORRECT NUMBERS. |
| | IT APPEARS TO BE MISSING LOADS SUCH AS LAUNDRY, SMALL |
| | APPLIANCE AND OTHERS. PLEASE CORRECT AS APPLICABLE. NEC |
| | 215.5 |
| | 5) PLEASE DETAIL APPLICABLE LIGHTING AND RECEPTACLES AS |
| | GROUND FAULT PROTECTED, ARC FAULT PROTECTED AND TAMPER |
| | RESISTANT AS PER NEC 210.12, NEC 406.4, NEC 406.12, NEC |
| | 406.4(D)(5) AND NEC 210.8 |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. |
| | |
| | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2020 7TH ED. |
| | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| | 7TH EDITION |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| | 7TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |