Plan Review Notes
Plan Review Notes For Permit 22040290
Permit Number 22040290
Review Stop B
Sequence Number 1
Notes
Date Text
2022-07-12 16:14:16SFR ADDITION - REMODEL
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE ROOFING SYSTEM PRODUCT APPROVAL
 LISTED ON THE DRAWINGS.
  
 2) PLEASE PROVIDE THE SINGLE HUNG WINDOW PRODUCT
 APPROVAL LISTED ON THE DRAWINGS.
  
 3) THE PROVIDED PRODUCT APPROVAL 17-0411.06 HAS EXPIRED
 AND IS NOT LISTED ON THE DRAWINGS. ALL PRODUCT
 APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY
 THE BUILDING DESIGNER OR BE LISTED ON THE DRAWINGS BY
 THE PRODUCT APPROVAL NUMBER. FBC WPB 107.3.4
  
 4) DRAWING S2.1 SHOWS ROOF FRAMING AS 2X8 JOIST SPACED
 24" OC. - DRAWING S1.1 SHOWS 2X12 RAFTERS SPACED 16" OC
 - PLEASE CLARIFY - R30 INSULATION WILL NOT WORK IN 2X8
 JOIST (A 1" AIR GAP IS REQUIRED BETWEEN THE INSULATION
 AND THE ROOF DECKING.
  
 5) PLEASE SHOW THE VENTILATION FOR THE RAFTER SPACE FBC
 R806.1 VENTILATION REQUIRED.
 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE
 CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF
 RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE
 SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE
 ENTRANCE OF RAIN OR SNOW.
  
  