| Plan Review Notes For Permit 22040290 |
| Permit Number |
22040290 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-07-12 16:14:16 | SFR ADDITION - REMODEL | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE ROOFING SYSTEM PRODUCT APPROVAL | | | LISTED ON THE DRAWINGS. | | | | | | 2) PLEASE PROVIDE THE SINGLE HUNG WINDOW PRODUCT | | | APPROVAL LISTED ON THE DRAWINGS. | | | | | | 3) THE PROVIDED PRODUCT APPROVAL 17-0411.06 HAS EXPIRED | | | AND IS NOT LISTED ON THE DRAWINGS. ALL PRODUCT | | | APPROVALS NEED TO BE REVIEWED AND MARKED APPROVED BY | | | THE BUILDING DESIGNER OR BE LISTED ON THE DRAWINGS BY | | | THE PRODUCT APPROVAL NUMBER. FBC WPB 107.3.4 | | | | | | 4) DRAWING S2.1 SHOWS ROOF FRAMING AS 2X8 JOIST SPACED | | | 24" OC. - DRAWING S1.1 SHOWS 2X12 RAFTERS SPACED 16" OC | | | - PLEASE CLARIFY - R30 INSULATION WILL NOT WORK IN 2X8 | | | JOIST (A 1" AIR GAP IS REQUIRED BETWEEN THE INSULATION | | | AND THE ROOF DECKING. | | | | | | 5) PLEASE SHOW THE VENTILATION FOR THE RAFTER SPACE FBC | | | R806.1 VENTILATION REQUIRED. | | | ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES FORMED WHERE | | | CEILINGS ARE APPLIED DIRECTLY TO THE UNDERSIDE OF ROOF | | | RAFTERS SHALL HAVE CROSS VENTILATION FOR EACH SEPARATE | | | SPACE BY VENTILATING OPENINGS PROTECTED AGAINST THE | | | ENTRANCE OF RAIN OR SNOW. | | | | | | |
|