| 2022-05-02 09:36:51 | FIRE REVIEW COMMENTS: | | | 1) PROVIDE DETAIL ON THE FIRE RATED ENTRY DOOR | | | REQUIREMENTS TO COMPLY WITH NFPA 80, CHAPTER 6. PER | | | NFPA 80, 3.3.50 A FIRE DOOR ASSEMBLY INCLUDES THE FIRE | | | DOOR, FRAME, HARDWARE, AND OTHER ACCESSORIES THAT | | | TOGETHER PROVIDE A SPECIFIC DEGREE OF FIRE PROTECTION | | | TO THE OPENING. | | | 2) PROVIDE THE TYPE OF CARPET TO BE INSTALLED TO COMPLY | | | WITH NFPA 101, 10.2.7.1 | | | 3) PROVIDE LOCATIONS AND TYPE OF SMOKE ALARMS TO BE | | | PROVIDED INCLUDING THE BEDROOM AND PROPOSED LIBRARY. | | | NFPA 101 31.3.4.5 | | | C. WALKER | | | 561-804-4762 | | | [email protected] | | | |
|