| Plan Review Notes For Permit 22040281 |
| Permit Number |
22040281 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-22 09:49:15 | FIRE REVIEW COMMENTS: | | | PROVIDE SPECIFIC LOCATION REQUIREMENTS FOR SMOKE ALARMS | | | ON THE ELECTRICAL PLAN. NFPA 72 29.8.3.4 | | | THE ELECTRICAL PLAN HAS A NOTE THAT ALL EXISTING | | | FLOORING IS TO BE REMOVED AND REPLACED THROUGHOUT THE | | | ENTIRE UNIT. PROVIDE SPECIFICATIONS ON FLOORING TO BE | | | INSTALLED FOR FIRE PERFORMANCE INCLUDING THE CRITICAL | | | RADIANT FLUX OF THE MATERIAL. NFPA 101 10.2.7 | | | FIRE REVIEW PERFORMED BY: | | | C. R. WALKER, SENIOR FIRE INSPECTOR | | | 561-804-4762 | | | [email protected] | | | |
|