| 2022-04-12 09:03:26 | JONATHAN BROOKS JR. | | | BUILDING PLANS EXAMINER | | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | | PHONE (561) 805-6656 | | | EMAIL: [email protected] | | | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | | RESULTS: DENIED | | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | | CITY HALL, OR EMAIL [email protected]. | | | | | | 1 FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | | APPROVAL FL16709-R9 SELECTED SYSTEM NO W-5; EXPOSURE | | | (C); ENCLOSURE (OPEN); ROOF HEIGHT (H < 15); ULTIMATE | | | WIND SPEED (180), IS NOT CORRECT. THE ENCLOSURE IS | | | (CLOSED) WIND SPEED 170 MPH. PLEASE SELECT THE CORRECT | | | OPTIONS. | | | 2. FBC B 107.2.1 FOR CLARITY PLEASE REVISE ROOF | | | DIAGRAM/SKETCH AND INCLUDE FLAT ROOF SLOPE(S). FLAT/LOW | | | SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. | | | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMEMTS. | | | |
|