Plan Review Notes
Plan Review Notes For Permit 22040244
Permit Number 22040244
Review Stop E
Sequence Number 1
Notes
Date Text
2022-04-25 14:20:01ELECTRICREVIEW FAILED
 1) PLEASE PROVIDE MORE DETAIL TO SHOW THE ELECTRIC
 PANEL IS NOT LOCATED INSIDE A BATHROOM AS PER NEC
 240.24 (E)
 2) PLEASE PROVIDE SPECIFICATIONS FOR TANKLESS WATER
 HEATER AND ANY ADDITIONAL LOADS. FBC 107.2
 3) PLEASEPROVIDE LOAD CALCULATIONS TO ENSURE ELECTRIC
 SERVICE IS ADEQUET TO SERVE THE LOAD. NEC 230.23(A)
 3) PLEASE PROVIDE DETAILS AS TO THE USE OF ALL
 RECEPTACLES. FBC 107.3
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  