| Plan Review Notes For Permit 22040244 |
| Permit Number |
22040244 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-25 14:20:01 | ELECTRICREVIEW FAILED | | | 1) PLEASE PROVIDE MORE DETAIL TO SHOW THE ELECTRIC | | | PANEL IS NOT LOCATED INSIDE A BATHROOM AS PER NEC | | | 240.24 (E) | | | 2) PLEASE PROVIDE SPECIFICATIONS FOR TANKLESS WATER | | | HEATER AND ANY ADDITIONAL LOADS. FBC 107.2 | | | 3) PLEASEPROVIDE LOAD CALCULATIONS TO ENSURE ELECTRIC | | | SERVICE IS ADEQUET TO SERVE THE LOAD. NEC 230.23(A) | | | 3) PLEASE PROVIDE DETAILS AS TO THE USE OF ALL | | | RECEPTACLES. FBC 107.3 | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|