Plan Review Notes
Plan Review Notes For Permit 22040203
Permit Number 22040203
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2022-04-08 09:54:26FIRE COMMENTS:
 1) THE SUBMITTAL DOES NOT INDICATE THE TYPE OF FLOORING
 TO BE INSTALLED. FLOORING MATERIALS MAY REQUIRE
 INFORMATION TO BE PROVIDED FOR FIRE PERFORMANCE
 INCLUDING THE CRITICAL RADIANT FLUX OF THE MATERIAL PER
 NFPA 101 10.2.7
 2) THE REMOVAL OF ANY WALLS MAY REQUIRE THE EVALUATION
 OF THE FIRE AND LIFE SAFETY SYSTEMS INCLUDING FIRE
 SPRINKLER IF APPLICABLE, AND FIRE ALARMS TO INSURE
 ADEQUATE COVERAGE.
 3) ALL EXISTING LIFE SAFETY SYSTEMS INCLUDING FIRE
 SPRINKLER IF APPLICABLE AND FIRE ALARM DEVICES MUST BE
 PROTECTED FROM DAMAGE AND MAINTAINED IN WORKING
 CONDITION DURING ALL PHASES OF DEMOLITION AND
 CONSTRUCTION.
 4) ANY MODIFICATIONS TO ANY LIFE SAFETY SYSTEM
 INCLUDING FIRE SPRINKLERS IF APPLICABLE AND FIRE ALARM
 SYSTEMS WILL REQUIRE SEPARATE PERMITS AND SHOP DRAWINGS
 AND THE WORK MUST BE CONDUCTED BY ONLY QUALIFIED
 CONTRACTORS.
 FIRE REVIEW PERFORMED BY:
 C.R. WALKER