| 2022-04-05 14:05:49 | PETER E VALENTI |
| | BUILDING PLANS EXAMINER II |
| | [email protected] |
| | 561 805 6673 |
| | |
| | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| | FBC B = FBC BUILDING |
| | FBC R = FBC RESIDENTIAL |
| | FBC EB = EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC M = FBC MECHANICAL |
| | FBC FG = FBC FUEL GAS |
| | |
| | BUILDING REVIEW DENIED: |
| | |
| | FBC B 107.2.1, THE SUBMITTED INFORMATION IS INCOMPLETE. |
| | PLEASE PROVIDE THE FOLLOWING: |
| | |
| | 1.) FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A |
| | SPAN |
| | OF 30 FEET OR GREATER IN ANY DIRECTION: |
| | A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE |
| | BASEPLATE/TIEDOWN DETAILS. |
| | B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE, |
| | INCLUDING WINDLOAD DESIGN PRESSURES. |
| | |
| | THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY |
| | A DESIGN PROFESSIONAL. |
| | NOTE: TENTS WITH A 30? SPAN ARE PERMITTED WITHOUT THE |
| | ADDITIONAL ENGINEERING |
| | AND STRUCTURAL CONNECTION DETAILS IF THE CONTRACTOR |
| | PLACES THE FOLLOWING NOTE ON THE |
| | PLAN ? THIS TENT SHALL BE REMOVED IF WINDS ARE |
| | EXPECTEDTO |
| | EXCEED 30 M.P.H. |
| | ***THERE WILL BE NO EXCEPTION TO THE ABOVE REQUIREMENT |
| | FOR TENTS WITH A SPAN IN ANY |
| | DIRECTION OF 40? OR MORE.*** |
| | |
| | 2.) FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH AN |
| | ?ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE |
| | FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN |
| | AREA |
| | AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS?. |
| | |
| | FLORIDA STATUTE 553.79 ?THREHOLD STRUCTURE? SHALL APPLY |
| | A. PROVIDE THRESHOLD INSPECTOR AGREEMENT ? WILL BE |
| | PROVIDED TO APPLICANT |
| | B. PROVIDE THRESHOLD INSPECTION PLAN |
| | C. PROVIDE AFFIDAVIT ?CERTIFICATE OF CODE COMPLIANCE? |
| | |
| | 3.) FBC B 3103.1.1, |
| | TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE |
| | STRUCTURAL STRENGTH, FIRE SAFETY, |
| | MEANS OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND |
| | SANITARY REQUIREMENTS OF THIS |
| | CODE AS NECESSARY TO ENSURE PUBLIC HEALTH, SAFETY AND |
| | GENERAL WELFARE. |
| | A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR |
| | STRUCTURES WITH SPANS OF 30 FEET OR GREATER. |
| | B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER |
| | NFPA 701 FOR EACH TENT |
| | C. MEANS OF EGRESS |
| | 1) OPEN SIDES ? NO LIFE SAFETY PLAN REQUIRED. |
| | 2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN |
| | A) STATE OCCUPANT LOAD. |
| | B) IDENTIFY MEANS OF EGRESS. |
| | C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO EXIT. |
| | D) PROVIDE FLOOR LAYOUT OF EVENT. |
| | D. ACCESSIBILITY |
| | 1) IDENTIFY ACCESSIBLE ROUTE ON SITE PLAN |
| | E. LIGHT |
| | 1) OPEN SIDES ? N/A |
| | 2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE |
| | F. VENTILATION |
| | 1) OPEN SIDES ? N/A |
| | 2) CLOSED SIDES ? PER SEC. 1203 |
| | G. SANITARY |
| | 1) IDENTIFY EXISTING PERMANENT FACILITIES ON SITE PLAN |
| | 2) PROVIDE PORTABLE FACILITIES PER TABLE 2902.1 |