Plan Review Notes
Plan Review Notes For Permit 22040185
Permit Number 22040185
Review Stop B
Sequence Number 1
Notes
Date Text
2022-04-05 14:05:49PETER E VALENTI
 BUILDING PLANS EXAMINER II
 [email protected]
 561 805 6673
  
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC M = FBC MECHANICAL
 FBC FG = FBC FUEL GAS
  
 BUILDING REVIEW DENIED:
  
 FBC B 107.2.1, THE SUBMITTED INFORMATION IS INCOMPLETE.
 PLEASE PROVIDE THE FOLLOWING:
  
 1.) FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH A
 SPAN
 OF 30 FEET OR GREATER IN ANY DIRECTION:
 A. PROVIDE DETAILS OF STRUCTURAL CONNECTIONS. INCLUDE
 BASEPLATE/TIEDOWN DETAILS.
 B. PROVIDE STRUCTURAL EVALUATION OF STRUCTURE,
 INCLUDING WINDLOAD DESIGN PRESSURES.
  
 THESE DOCUMENTS SHALL BE REVIEWED, SIGNED AND SEALED BY
 A DESIGN PROFESSIONAL.
 NOTE: TENTS WITH A 30? SPAN ARE PERMITTED WITHOUT THE
 ADDITIONAL ENGINEERING
 AND STRUCTURAL CONNECTION DETAILS IF THE CONTRACTOR
 PLACES THE FOLLOWING NOTE ON THE
 PLAN ? THIS TENT SHALL BE REMOVED IF WINDS ARE
 EXPECTEDTO
 EXCEED 30 M.P.H.
 ***THERE WILL BE NO EXCEPTION TO THE ABOVE REQUIREMENT
 FOR TENTS WITH A SPAN IN ANY
 DIRECTION OF 40? OR MORE.***
  
 2.) FOR TEMPORARY MEMBRANE STRUCTURES (TENTS) WITH AN
 ?ASSEMBLY OCCUPANCY CLASSIFICATION AS DEFINED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA
 AND AN OCCUPANT CONTENT OF GREATER THAN 500 PERSONS?.
  
 FLORIDA STATUTE 553.79 ?THREHOLD STRUCTURE? SHALL APPLY
 A. PROVIDE THRESHOLD INSPECTOR AGREEMENT ? WILL BE
 PROVIDED TO APPLICANT
 B. PROVIDE THRESHOLD INSPECTION PLAN
 C. PROVIDE AFFIDAVIT ?CERTIFICATE OF CODE COMPLIANCE?
  
 3.) FBC B 3103.1.1,
 TEMPORARY STRUCTURES AND USES SHALL CONFORM TO THE
 STRUCTURAL STRENGTH, FIRE SAFETY,
 MEANS OF EGRESS, ACCESSIBILITY, LIGHT, VENTILATION AND
 SANITARY REQUIREMENTS OF THIS
 CODE AS NECESSARY TO ENSURE PUBLIC HEALTH, SAFETY AND
 GENERAL WELFARE.
 A. STRUCTURAL STRENGTH PER FBC CHPT. 16 ? FOR
 STRUCTURES WITH SPANS OF 30 FEET OR GREATER.
 B. FIRE SAFETY ? PROVIDE FLAME SPREAD TEST REPORTS PER
 NFPA 701 FOR EACH TENT
 C. MEANS OF EGRESS
 1) OPEN SIDES ? NO LIFE SAFETY PLAN REQUIRED.
 2) CLOSED SIDES ? PROVIDE LIFE SAFETY PLAN
 A) STATE OCCUPANT LOAD.
 B) IDENTIFY MEANS OF EGRESS.
 C) IDENTIFY PATH OF TRAVEL ? 100 FT. OR LESS TO EXIT.
 D) PROVIDE FLOOR LAYOUT OF EVENT.
 D. ACCESSIBILITY
 1) IDENTIFY ACCESSIBLE ROUTE ON SITE PLAN
 E. LIGHT
 1) OPEN SIDES ? N/A
 2) CLOSED SIDES ? PER SEC. 1008.2.1 > 1 FOOT CANDLE
 F. VENTILATION
 1) OPEN SIDES ? N/A
 2) CLOSED SIDES ? PER SEC. 1203
 G. SANITARY
 1) IDENTIFY EXISTING PERMANENT FACILITIES ON SITE PLAN
 2) PROVIDE PORTABLE FACILITIES PER TABLE 2902.1