| 2022-05-24 12:11:53 | 1ST PLUMBING REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. 2017 WPB AMENDS 107.2.1 - PLEASE INCLUDE AN EXISTING | | | FLOOR PLAN AND A PROPOSED FLOOR PLAN TO INDICATE THE | | | CHANGES BEING MADE. | | | | | | 2. 2020 FPC 1002.1 - THEE WASHING MACHINE IS NOT SHOWN | | | WITH A TRAP. ALL FIXTURES SHALL BE TRAPPED. | | | | | | 3. 2017 WPB AMENDS 107.3.5.1.3 - THE PLUMBING RISER | | | NEEDS TO INCLUDE THE NEW WALL MOUNTED WATER CLOSET | | | CONNECTION AND OTHER AFFECTED FIXTURES. THE WATER | | | CLOSETS NEW CONNECTION WILL BE ABOVE THE FLOOR AND WILL | | | NEED TO BE SHOWN IN ORDER TO REVIEW FOR CODE | | | COMPLIANCE. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|