| Plan Review Notes For Permit 22040109 |
| Permit Number |
22040109 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-04 08:55:56 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | | | FLORIDA BUILDING CODE 2020 7TH EDITION | | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED | | | NFPA 70 2017 EDITION | | | | | | JAKE LEAHY BN, BU, PX | | | ELECTRICAL PLANS EXAMINER II | | | 561-805-6713 | | | [email protected] | | | | | | 1) LOAD ON MDPA IS ABOVE 1600 AMPERES AND 1520 AMPERES | | | OF THE FEEDERS, PLEASE PROVIDE DOCUMENTATION FOR SAFE | | | LOAD LEVELS. 215.5 | | | | | | 2) PLEASE PROVIDE A COST BREAK DOWN OF MATERIALS AND | | | LABOR OR A SIGNED CONTRACT WITH THE OWNER. |
|