2022-05-04 08:55:56ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 FLORIDA BUILDING CODE 2020 7TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 7TH ED
 NFPA 70 2017 EDITION
  
 JAKE LEAHY BN, BU, PX
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 1) LOAD ON MDPA IS ABOVE 1600 AMPERES AND 1520 AMPERES
 OF THE FEEDERS, PLEASE PROVIDE DOCUMENTATION FOR SAFE
 LOAD LEVELS. 215.5
  
 2) PLEASE PROVIDE A COST BREAK DOWN OF MATERIALS AND
 LABOR OR A SIGNED CONTRACT WITH THE OWNER.