| 2022-09-07 12:15:04 | 1A) NOA 18-0919.07 PAGE 11OF 27 WOOD INSULATED DECK |
| | SYSTEMS TYPE A. PREVIOUS REVIEW (3RD) NO SUB-SYSTEM WAS |
| | HIGHLIGHTED. THIS REVIEW 4TH THIS REVIEW OPTION # 1 IS |
| | HIGHLIGHTED. |
| | |
| | 1B) THIS REVIEW OPTION # 1 HIGHLIGHTED, MAXIMUM DESIGN |
| | PRESSURE: -45 PSF WITH LIMITATION # 7, ALLOWING FOR |
| | ENHANCED FASTENING. THE ENGINEER OF RECORD CAME BACK |
| | WITH SIGNED & SEALED DOCUMENT FOR THE ENHANCED |
| | FASTENING, THE SAME SPACING AND ROWS OF FASTENERS AS |
| | REQUIRED FOR ROOF ZONE ONE. NO ENHANCED FASTENING. THE |
| | ENGINEER OF RECORD MUST FOLLOW RAS 117 SECTION 10 FOR |
| | ENHANCED FASTENING FOR ZONES 2 & 3 SHOW WORK SEE |
| | EXAMPLE 10.3. |
| | LAST REVIEW COMMENT. NOA 18-0919.07PAGE 11 OF 27 WOOD |
| | INSULATED DECK SYSTEMS TYPE A ENGINEERS RESPONSE STATES |
| | SEE OPTION # 1, NOT HIGHLIGHTED PLEASE HIGHLIGHT. FOR |
| | ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING |
| | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF |
| | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF |
| | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. |
| | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH |
| | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE |
| | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION |
| | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED |
| | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. |
| | 1609.6.4.4.1 COMPONENTS & CLADDING. |
| | JAMES A. WITMER BN, PX, SFP, CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES |
| | DEPARTMENT |
| | 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| | TEL: 561-805-6717 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |