Plan Review Notes
Plan Review Notes For Permit 22040093
Permit Number 22040093
Review Stop R
Sequence Number 4
Notes
Date Text
2022-09-07 12:15:041A) NOA 18-0919.07 PAGE 11OF 27 WOOD INSULATED DECK
 SYSTEMS TYPE A. PREVIOUS REVIEW (3RD) NO SUB-SYSTEM WAS
 HIGHLIGHTED. THIS REVIEW 4TH THIS REVIEW OPTION # 1 IS
 HIGHLIGHTED.
  
 1B) THIS REVIEW OPTION # 1 HIGHLIGHTED, MAXIMUM DESIGN
 PRESSURE: -45 PSF WITH LIMITATION # 7, ALLOWING FOR
 ENHANCED FASTENING. THE ENGINEER OF RECORD CAME BACK
 WITH SIGNED & SEALED DOCUMENT FOR THE ENHANCED
 FASTENING, THE SAME SPACING AND ROWS OF FASTENERS AS
 REQUIRED FOR ROOF ZONE ONE. NO ENHANCED FASTENING. THE
 ENGINEER OF RECORD MUST FOLLOW RAS 117 SECTION 10 FOR
 ENHANCED FASTENING FOR ZONES 2 & 3 SHOW WORK SEE
 EXAMPLE 10.3.
 LAST REVIEW COMMENT. NOA 18-0919.07PAGE 11 OF 27 WOOD
 INSULATED DECK SYSTEMS TYPE A ENGINEERS RESPONSE STATES
 SEE OPTION # 1, NOT HIGHLIGHTED PLEASE HIGHLIGHT. FOR
 ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION / DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  