| Plan Review Notes For Permit 22040093 |
| Permit Number |
22040093 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-08-16 10:38:18 | 1A) 3RD REQUEST. SEMI-COMPLIED. SUBMITTED NOA | | | 18-0919.07PAGE 11 OF 27 WOOD INSULATED DECK SYSTEMS | | | TYPE A. CALLED THE ENGINEER NO SUBSYSTEM HIGHLIGHTED. | | | ENGINEERS RESPONSE STATES SEE OPTION # 1 NOT | | | HIGHLIGHTED. | | | | | | 1B) NEW COMMENT. NOA 18-0919.07PAGE 11 OF 27 WOOD | | | INSULATED DECK SYSTEMS TYPE A ENGINEERS RESPONSE STATES | | | SEE OPTION # 1, NOT HIGHLIGHTED PLEASE HIGHLIGHT. FOR | | | ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING | | | SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF | | | ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF | | | ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3. | | | FASTENER DENSITIES SHALL BE INCREASED FOR BOTH | | | INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE | | | WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION | | | PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED | | | PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT. | | | 1609.6.4.4.1 COMPONENTS & CLADDING | | | | | | 1C) NEW COMMENT. THE TITLE-SHEET HAS THE WIND LOAD | | | SCHEDULE FOR ROOF & WALL EFFECTIVE WIND AREA. PLEASE | | | NOTE THE EFFECTIVE WIND AREA FOR ROOFS IN ALL ZONES IS | | | TAKEN AT 10 SQ. FT. (FASTENERS). VASD ROOF LOADS (132) | | | EXPOSURE C 15MRH ZONE # 1 +15.4/ -37.9, ZONE 2 +15.4/ | | | -63.6 & ZONE 3 +15.4/ -95.7. | | | |
|