Plan Review Notes
Plan Review Notes For Permit 22040093
Permit Number 22040093
Review Stop R
Sequence Number 3
Notes
Date Text
2022-08-16 10:38:181A) 3RD REQUEST. SEMI-COMPLIED. SUBMITTED NOA
 18-0919.07PAGE 11 OF 27 WOOD INSULATED DECK SYSTEMS
 TYPE A. CALLED THE ENGINEER NO SUBSYSTEM HIGHLIGHTED.
 ENGINEERS RESPONSE STATES SEE OPTION # 1 NOT
 HIGHLIGHTED.
  
 1B) NEW COMMENT. NOA 18-0919.07PAGE 11 OF 27 WOOD
 INSULATED DECK SYSTEMS TYPE A ENGINEERS RESPONSE STATES
 SEE OPTION # 1, NOT HIGHLIGHTED PLEASE HIGHLIGHT. FOR
 ALL ROOFING PRODUCTS PLEASE IDENTIFY ALL ROOFING
 SUB-SYSTEMS AND THEIR ASSOCIATED PRESSURES FOR ROOF
 ZONE # 1. REVIEW THE PRODUCT APPROVAL LIMITATIONS, IF
 ENHANCED FASTENING IS ALLOWED FOR ROOF ZONES 2 & 3.
 FASTENER DENSITIES SHALL BE INCREASED FOR BOTH
 INSULATION & THE BASE SHEET AS CALCULATED IN COMPLIANCE
 WITH ROOFING APPLICATION STANDARDS RAS 117. CALCULATION
 PREPARED, SIGNED AND SEALED BY A FLORIDA REGISTERED
 PROFESSIONAL ENGINEER OR REGISTERED ARCHITECT.
 1609.6.4.4.1 COMPONENTS & CLADDING
  
 1C) NEW COMMENT. THE TITLE-SHEET HAS THE WIND LOAD
 SCHEDULE FOR ROOF & WALL EFFECTIVE WIND AREA. PLEASE
 NOTE THE EFFECTIVE WIND AREA FOR ROOFS IN ALL ZONES IS
 TAKEN AT 10 SQ. FT. (FASTENERS). VASD ROOF LOADS (132)
 EXPOSURE C 15MRH ZONE # 1 +15.4/ -37.9, ZONE 2 +15.4/
 -63.6 & ZONE 3 +15.4/ -95.7.
  