| Plan Review Notes For Permit 22040093 |
| Permit Number |
22040093 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-05-17 16:42:28 | 1ST REVIEW FBC-2020 PLUMBING | | | PERMIT- 22040093 | | | 5/17/22 | | | | | | CODES IN EFFECT: | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | | FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 | | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | | FS- FLORIDA STATUTES | | | FAC- FLORIDA ADMINISTRATIVE CODE | | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | | | PLAN REVIEW RESULTS: DENIED. | | | | | | 1) THE OCCUPANT LOAD OF THE DAY CARE CENTER WILL BE | | | INCREASED WITH THE NEW ADDITION WHICH MEANS ADDITIONAL | | | PLUMBING FIXTURES MAY BE REQUIRED- SEE SECS. 1102.1 AND | | | 810.2 FBC EX. PLEASE PROVIDE PLUMBING FIXTURE | | | CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P. | | | PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND | | | PROVIDED NUMBER OF FIXTURES. | | | | | | 2) PLEASE NOTE THAT INSTALLATION OF NEW REQUIRED | | | PLUMBING FIXTURES WILL REQUIRE PLUMBING AND | | | ACCESSIBILITY PLANS TO BE SUBMITTED- SEC. 107.2.1 & | | | 107.3.5.1 WPB. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RE-SUBMITTAL FORM. | | | | | | CHRISTOPHER L. COLE | | | MECHANICAL/PLUMBING PLANS EXAMINER | | | 401 CLEMATIS STREET | | | WEST PALM BEACH FL 33401 | | | 561-805-6719 | | | [email protected] | | | |
|