Plan Review Notes
Plan Review Notes For Permit 22040093
Permit Number 22040093
Review Stop P
Sequence Number 1
Notes
Date Text
2022-05-17 16:42:281ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22040093
 5/17/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE OCCUPANT LOAD OF THE DAY CARE CENTER WILL BE
 INCREASED WITH THE NEW ADDITION WHICH MEANS ADDITIONAL
 PLUMBING FIXTURES MAY BE REQUIRED- SEE SECS. 1102.1 AND
 810.2 FBC EX. PLEASE PROVIDE PLUMBING FIXTURE
 CALCULATIONS IN ACCORDANCE WITH TABLE 403.1 FBC P.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED NUMBER OF FIXTURES.
  
 2) PLEASE NOTE THAT INSTALLATION OF NEW REQUIRED
 PLUMBING FIXTURES WILL REQUIRE PLUMBING AND
 ACCESSIBILITY PLANS TO BE SUBMITTED- SEC. 107.2.1 &
 107.3.5.1 WPB.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  