| 2022-04-29 12:34:04 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | 1) THERE ARE INDICATIONS OF A 2 NEW EXTERIOR EXTERIOR |
| | DOOR THAT DO NOT HAVE AN EXIT SIGN OVER IT. |
| | |
| | PER NFPA 17 EXISTING DAYCARE OCCUPANCIES |
| | |
| | 17.2.8 ILLUMINATION OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL BE |
| | ILLUMINATED IN ACCORDANCE WITH SECTION 7.8. |
| | |
| | 17.2.10 MARKING OF MEANS OF EGRESS. MEANS OF EGRESS |
| | SHALL HAVE |
| | SIGNS IN ACCORDANCE WITH SECTION 7.10 |
| | |
| | PLEASE REVIEW AND OR PROVIDE DETAILED FIRE CODE |
| | REFERENCES THAT INDICATES IT IS NOT REQUIRED. |
| | |
| | |
| | |
| | 1A) THERE ARE NO INDICATIONS OF EMEGERNCY LIGHTING IN |
| | THE NEW ADDITION. |
| | |
| | 17.2.9 EMERGENCY LIGHTING. EMERGENCY LIGHTING SHALL BE |
| | PROVIDED IN |
| | ACCORDANCE WITH SECTION 7.9 IN THE FOLLOWING AREAS: |
| | (1) INTERIOR STAIRS AND CORRIDORS |
| | (2) ASSEMBLY USE SPACES |
| | (3) FLEXIBLE AND OPEN PLAN BUILDINGS |
| | (4) INTERIOR OR LIMITED ACCESS PORTIONS OF BUILDINGS |
| | (5) SHOPS AND LABORATORIES |
| | |
| | PLEASE REVIEW AND OR PROVIDE DETAILED FIRE CODE |
| | REFERENCES THAT INDICATES IT IS NOT REQUIRED. |
| | |
| | |
| | 2) THERE DOES NOT APPEAR TO BE DOOR HARDWARE & LOCKING |
| | PER NFPA REQUIREMENTS. |
| | |
| | 17.2.2 MEANS OF EGRESS COMPONENTS. |
| | 17.2.2.1 COMPONENTS PERMITTED. COMPONENTS OF MEANS OF |
| | EGRESS |
| | SHALL BE LIMITED TO THE TYPES DESCRIBED IN 17.2.2.2 |
| | THROUGH 17.2.2.10. |
| | 17.2.2.2 DOORS. |
| | 17.2.2.2.1 GENERAL. DOORS COMPLYING WITH 7.2.1 SHALL BE |
| | PERMITTED. |
| | |
| | 7.2.1.5 LOCKS, LATCHES, AND ALARM DEVICES. |
| | |
| | 7.2.1.5.1 DOOR LEAVES SHALL BE ARRANGED TO BE OPENED |
| | READILY FROM THE |
| | EGRESS SIDE WHENEVER THE BUILDING IS OCCUPIED |
| | |
| | 7.2.1.5.5 KEY-OPERATED LOCKS. |
| | 7.2.1.5.5.1* EXTERIOR DOOR ASSEMBLIES SHALL BE |
| | PERMITTED TO HAVE KEY OPERATED LOCKS FROM THE EGRESS |
| | SIDE, PROVIDED THAT ALL OF THE FOLLOWING |
| | CRITERIA ARE MET: |
| | (1) THIS ALTERNATIVE IS PERMITTED IN CHAPTERS 11 |
| | THROUGH 43 FOR THE |
| | SPECIFIC OCCUPANCY. |
| | (2) A READILY VISIBLE, DURABLE SIGN IN LETTERS NOT LESS |
| | THAN 1 IN. (25 MM) |
| | HIGH ON A CONTRASTING BACKGROUND THAT READS AS FOLLOWS |
| | IS LOCATED |
| | ON OR ADJACENT TO THE DOOR LEAF: THIS DOOR TO REMAIN |
| | UNLOCKED WHEN THE BUILDING IS OCCUPIED. |
| | (3) THE LOCKING DEVICE IS OF A TYPE THAT IS READILY |
| | DISTINGUISHABLE AS |
| | LOCKED. |
| | (4) A KEY IS IMMEDIATELY AVAILABLE TO ANY OCCUPANT |
| | INSIDE THE BUILDING |
| | WHEN IT IS LOCKED |
| | |
| | 7.2.1.5.10* A LATCH OR OTHER FASTENING DEVICE ON A DOOR |
| | LEAF SHALL BE |
| | PROVIDED WITH A RELEASING DEVICE THAT HAS AN OBVIOUS |
| | METHOD OF OPERATION |
| | AND THAT IS READILY OPERATED UNDER ALL LIGHTING |
| | CONDITIONS |
| | |
| | 7.2.1.5.10.1 THE RELEASING MECHANISM FOR ANY LATCH |
| | SHALL BE LOCATED AS |
| | FOLLOWS: |
| | (1) NOT LESS THAN 34 IN. (865 MM) ABOVE THE FINISHED |
| | FLOOR FOR OTHER |
| | THAN EXISTING INSTALLATIONS |
| | (2) NOT MORE THAN 48 IN. (1220 MM) ABOVE THE FINISHED |
| | FLOOR |
| | 7.2.1.5.10.2 THE RELEASING MECHANISM SHALL OPEN THE |
| | DOOR LEAF WITH NOT |
| | MORE THAN ONE RELEASING OPERATION, UNLESS OTHERWISE |
| | SPECIFIED IN |
| | 7.2.1.5.10.3, 7.2.1.5.10.4, 7.2.1.5.10.6, OR |
| | 7.2.1.5.10.7 |
| | |
| | PLEASE REVIEW AND PROVIDE DETAILS IN COMPLIANCE. |
| | |
| | |
| | 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |