 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 18-1105.03 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF UNDERLAYMENT
 SYSTEM TO BE USED. ALL APPLICABLE DETAILS AND
 ATTACHMENTS MUST BE CLEARLY IDENTIFIED ON THE PRODUCT
 APPROVAL DRAWINGS. DETAILS AND ATTACHMENTS NOT
 SPECIFICALLY COVERED IN PRODUCT APPROVALS WILL NEED
 SITE-SPECIFIC ENGINEERING.
 2. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA
 17-0322.03 HAS EXPIRED AND IS NO LONGER VALID. PLEASE
 PROVIDE A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA???S FOR THE PROPOSED ROOFING TILE
 ADHESIVE TO BE USED. INCLUDE COVER PAGE, EVALUATION
 REPORTS AND INSTALLATION INSTRUCTIONS FOR SYSTEM USED.
 ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 3. FBC B 107.2.1. REVISE SUBMITTED ROOF COVERING
 ATTACHMENT CALCULATIONS PREPARED, SIGNED AND SEALED BY
 A FLORIDA REGISTERED PROFESSIONAL ENGINEER TO UPDATE
 ROOF TILE NOA TO THE CURRENT APPROVED VERSION
 MIAMI-DADE NOA NO 21-0420.04
 4. FBC R 301 FAC9N-3. HIP & RIDGE INSTALLATION. IF
 USING WOOD OR PLASTIC, PLEASE PROVIDE PAGE #14 HIP &
 RIDGE INSTALLATION OF THE FLORIDA HIGH WIND CONCRETE
 AND CLAY TILE INSTALLATION MANUEL 6TH EDITION. PLEASE
 INDICATE (HIGHLIGHT/CIRCLE) THE FOLLOWING: FIELD TILE
 ATTACHMENT; STRUCTURAL SUPPORT; MEMBER ATTACHMENT; TRIM
 TILE ATTACHMENT; WEATHER BLOCKING & FINISH. ALL
 APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY
 IDENTIFIED. NOTE: DRAWING PA-20 DO NOT SHOW HOW WOOD
 NAILER IS ATTACHED TO STRUCTURE.
 5. FBC B 107.2.1. SUBMITTED MIAMI-DADE COUNTY NOA NO.
 18-0110.05 HAS EXPIRED AND IS NO LONGER VALID. PROVIDE
 A COMPLETE SET OF 2020 CODE VERSION PRODUCT
 APPROVALS/NOA'S FOR THE PROPOSED ROOF HATCH SYSTEM TO
 BE USED. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST BE
 CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 DETAILS AND ATTACHMENTS NOT SPECIFICALLY COVERED IN
 PRODUCT APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING.
 6. FBC B 107.2.1. REVISE SUBMITTED ROOF HATCH
 ATTACHMENT CALCULATIONS PREPARED, SIGNED AND SEALED BY
 A FLORIDA REGISTERED PROFESSIONAL ENGINEER TO UPDATE
 ROOF HATCH NOA TO THE CURRENT APPROVED VERSION
 MIAMI-DADE NOA NO 21-1201.02
 7. FBC B 107.3.4.1. SUBMIT ALL PRODUCT
 APPROVALS/NOA???S THAT SHALL BE USED FOR THIS ROOFING
 PROJECT TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL. ALL APPLICABLE DETAILS AND ATTACHMENTS MUST
 BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS.
 NOTE: MUST BE SIGNED BY ARCHITECT/ENGINEER BEFORE
 SUBMITTING.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  