Plan Review Notes
Plan Review Notes For Permit 22040030
Permit Number 22040030
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-14 12:38:03****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
  
 THE FOLLOWING ITEMS ARE REQUIRED PRIOR TO ISSUANCE OF A
 DEMO PERMIT PER FLORIDA BUILDING CODE, BUILDING 3303:
  
 1. UTILITY RELEASE - CITY OF WEST PALM BEACH WATER
 DEPARTMENT, ON THEIR FORM "DEMOLITION APPLICATION"
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
  IF A HYDRANT METER OR BACKFLOW PREVENTER IS DESIRED,
 THEN A PARTIAL RELEASE WILL BE NOTED ON THEIR FORM.
  
 FAX THE COMPLETED "DEMOLITION APPLICATION" FORM TO
 561-822-2183. PROVIDE THE FORM SIGNED BY UTILITIES WHEN
 RESUBMITTING.
  
 THIS IS REQUIRED EVEN IF YOU ARE NOT REQUESTING A METER
 PULL DUE TO THE DEMOLITION ACTIVITY. THIS IS REQUIRED
 BY THE WEST PALM BEACH UTILITIES DEPARTMENT.
  
 2. COMPLETE THE DEMO DEBRIS FORM, FEES WILL BE ADDED TO
 YOUR PERMIT "DEMOLITION DEBRIS DISPOSAL FEE":
  
 HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B
 UILDING-PERMIT-FORMS
  
 IF FORMS ARE UNAVAILABLE ONLINE, REQUEST AT [email protected].
  
 3. NATURE OF INTERIOR DEMO IS NOT CLEAR, FBC 107
 PROVIDE A PLAN.
  
 4. PROVIDE A STORMWATER POLLUTION PREVENTION PLAN.
  
 5. DEPENDING ON SCOPE OF INTERIOR DEMO, AN ELECTRICAL
 SUB MAY BE REQUIRED.