| Plan Review Notes For Permit 22040018 |
| Permit Number |
22040018 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-06-29 08:28:42 | PETER E VALENTI | | | BUILDING PLANS EXAMINER II | | | [email protected] | | | 561 805 6673 | | | | | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | | FBC B = FBC BUILDING | | | FBC R = FBC RESIDENTIAL | | | FBC EB = EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC M = FBC MECHANICAL | | | FBC FG = FBC FUEL GAS | | | | | | BUILDING REVIEW DENIED: | | | | | | 1.) FBC B 107.2.1, ON THE SCHEDULE FOR OPENINGS, | | | OPENINGS # 3 - 7 (WOOD SUBSTRATE) NEEDS TO BE CORECTED | | | TO THE SAME AS WHAT WAS IDENTIFIED WITHIN THE PRODUCT | | | APPROVAL AS 1/4" LAG SCREWS. | | | 2.) FBC B 107.2.1, ON THE SCHEDULE FOR OPENINGS AT | | | COLUMN #2, ALL OPENINGS ARE MISSING THE + AND - | | | PRESSURES. | | | 3.) FBC B 107.2.1, ON THE SCHEDULE FOR OPENINGS AT | | | COLUMN #6, ALL OPENINGS ARE MISSING THE VERTICAL OR | | | HORIZONTAL ORIENTATION OF SHUTTER SPANS. THEY APPEAR TO | | | BE VERYTICAL. | | | 4.) FBC B 107.2.1, PLEASE PROVIDE A LAYOUT/SKETCH | | | SHOWING THE LOCATION OF EACH OPENING. THIS | | | LAYOUT/SKETCH MUST CORRELATE WITH THE OPENING SCHEDULE. |
|