| Plan Review Notes For Permit 22031580 |
| Permit Number |
22031580 |
|
| Review Stop |
R |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2022-12-16 08:55:57 | ROOFING REVIEW | | | | | | ORIGINAL COMMENT: | | | 1) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | | | RESPONSE: | | | FASTENING OPTION #2 SELECTED ON PAGE 53 NOA 18-0919.12 | | | CANNOT BE USED. THIS ASSEMBLY IS LIMITED BY GENERAL | | | LIMITATION #9. THIS LIMITATION DOESN'T ALLOW NAIL | | | ENHANCEMENT. SEE GENERAL LIMITATION #9 ON LAST PAGE OF | | | NOA. | | | | | | NOTE: ENGINEER NEEDS TO REVISE RAS 117 CALCULATIONS. | | | SEE COMMENT ABOVE. | | | AND NEEDS TO REFERENCE THE SPECIFIC FASTENING OPTION | | | FROM NOA 18-0919.12. | | | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | | | | | | | |
|