Plan Review Notes
Plan Review Notes For Permit 22031580
Permit Number 22031580
Review Stop B
Sequence Number 3
Notes
Date Text
2022-12-16 08:50:11RESIDENTIAL (R3)ALTERATION THIRD BUILDING REVIEW
 COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22031580
 849 ARDMORE RD
  
 PROVISO: NOTE:
 BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO
 MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER
 THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID
 CONFLICTS/DELAYS. REVISION FEES MAY APPLY.
  
 ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION
 IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED
 INFORMATION BEFORE PERMIT ISSUANCE.
  
  
  
 1- OK.
 2- OK.
 3- OK.
 4- OK.
 5- OK.
 6- OK.
 7- OK.
 8- OK.
 9- OK.
 10-OK.
 11-OK.
  
 ORIGINAL COMMENT:
 12- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
  
 RESPONSE:
 DRAWING A102 WAS REVISED TO SHOW OUTSWING DOOR. IT IS
 NOT CLEAR IF THE ENTRY DOOR IS THE SAME TYPE AS THE
 FRENCH DOORS TYPE SHOWN ON THE BEDROOM #3 AND KITCHEN
 AREAS.
 DOORS PRODUCT APPROVALS UPLOADED TO PROJECTDOX DON'T
 HAVE THE REVIEW STAMP OF THE DESIGNER OF RECORD. IT IS
 VERY CONFUSING TO KNOW WHICH ARE THE PRODUCT APPROVALS
 REVIEWED BY THE DESIGNER OF RECORD. PLEASE STAMP THE
 REVIEW STAMP ON ALL PRODUCT APPROVALS AND CLEARLY
 SPECIFY IF ENTRY DOOR OR REAR FRENCH DOORS TO AVOID
 MORE CONFLICT/CONFUSION.
 NOTE: PLEASE COORDINATE WITH THE PERMIT LIBRARIAN TO
 SEE WHAT PRODUCT APPROVALS NEED TO BE REMOVED TO AVOID
 MORE CONFLICTS/DELAYS.
  
  
 B)REAR FRENCH DOORS.
  
 RESPONSE:
 PLEASE COORDINATE WITH ITEM ABOVE TO AVOID MORE
 CONFLICTS/DELAYS.
  
 E)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
  
 RESPONSE:
 NEED TO SPECIFY MULLION SIZES, INCLUDING MULLIONS AT
 THE BAY WINDOWS.
  
 ORIGINAL COMMENT:
 H) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 RESPONSE:
 FASTENING OPTION #2 SELECTED ON PAGE 53 NOA 18-0919.12
 CANNOT BE USED. THIS ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9. THIS LIMITATION DOESN'T ALLOW NAIL
 ENHANCEMENT. SEE GENERAL LIMITATION #9 ON LAST PAGE OF
 NOA.
  
 NOTE: ENGINEER NEEDS TO REVISE RAS 117 CALCULATIONS.
 SEE COMMENT ABOVE.
 AND NEEDS TO REFERENCE THE SPECIFIC FASTENING OPTION
 FROM NOA 18-0919.12.
  
 ORIGINAL COMMENT:
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 RESPONSE:
 COORDINATE ALL PRODUCT APPROVALS WITH CONTRACTOR. SEE
 COMMENT 12(A) ABOVE.
  
  
 14-OK.
 15-OK.
 16-OK.
 17-OK.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712
 [email protected]
  
  
  