| 2022-12-16 08:50:11 | RESIDENTIAL (R3)ALTERATION THIRD BUILDING REVIEW |
| | COMMENTS |
| | CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| | PERMIT #22031580 |
| | 849 ARDMORE RD |
| | |
| | PROVISO: NOTE: |
| | BUILDING REVIEW MAY BE APPROVED WITH PROVISO. PROVISO |
| | MEANS CONTRACTOR WILL SUBMIT REQUIRED INFORMATION AFTER |
| | THE PERMIT IS ISSUED BUT BEFORE INSPECTIONS TO AVOID |
| | CONFLICTS/DELAYS. REVISION FEES MAY APPLY. |
| | |
| | ***IMPORTANT****CONTRACTOR TO ADVICE IF PROVISO OPTION |
| | IS PREFERRED AT THIS TIME OR IF RE-SUBMITTING REQUIRED |
| | INFORMATION BEFORE PERMIT ISSUANCE. |
| | |
| | |
| | |
| | 1- OK. |
| | 2- OK. |
| | 3- OK. |
| | 4- OK. |
| | 5- OK. |
| | 6- OK. |
| | 7- OK. |
| | 8- OK. |
| | 9- OK. |
| | 10-OK. |
| | 11-OK. |
| | |
| | ORIGINAL COMMENT: |
| | 12- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC |
| | 61G20-3.001 FOR |
| | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED |
| | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW |
| | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL |
| | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY |
| | DESIGNER OF RECORD PRIOR TO SUBMITTAL): |
| | |
| | A)INSWING ENTRY DOOR AS SHOWN ON PLANS. |
| | |
| | RESPONSE: |
| | DRAWING A102 WAS REVISED TO SHOW OUTSWING DOOR. IT IS |
| | NOT CLEAR IF THE ENTRY DOOR IS THE SAME TYPE AS THE |
| | FRENCH DOORS TYPE SHOWN ON THE BEDROOM #3 AND KITCHEN |
| | AREAS. |
| | DOORS PRODUCT APPROVALS UPLOADED TO PROJECTDOX DON'T |
| | HAVE THE REVIEW STAMP OF THE DESIGNER OF RECORD. IT IS |
| | VERY CONFUSING TO KNOW WHICH ARE THE PRODUCT APPROVALS |
| | REVIEWED BY THE DESIGNER OF RECORD. PLEASE STAMP THE |
| | REVIEW STAMP ON ALL PRODUCT APPROVALS AND CLEARLY |
| | SPECIFY IF ENTRY DOOR OR REAR FRENCH DOORS TO AVOID |
| | MORE CONFLICT/CONFUSION. |
| | NOTE: PLEASE COORDINATE WITH THE PERMIT LIBRARIAN TO |
| | SEE WHAT PRODUCT APPROVALS NEED TO BE REMOVED TO AVOID |
| | MORE CONFLICTS/DELAYS. |
| | |
| | |
| | B)REAR FRENCH DOORS. |
| | |
| | RESPONSE: |
| | PLEASE COORDINATE WITH ITEM ABOVE TO AVOID MORE |
| | CONFLICTS/DELAYS. |
| | |
| | E)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE |
| | TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL). |
| | |
| | RESPONSE: |
| | NEED TO SPECIFY MULLION SIZES, INCLUDING MULLIONS AT |
| | THE BAY WINDOWS. |
| | |
| | ORIGINAL COMMENT: |
| | H) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY |
| | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE |
| | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. |
| | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN |
| | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED |
| | RAS 117 CALCULATIONS ARE REQUIRED. |
| | |
| | RESPONSE: |
| | FASTENING OPTION #2 SELECTED ON PAGE 53 NOA 18-0919.12 |
| | CANNOT BE USED. THIS ASSEMBLY IS LIMITED BY GENERAL |
| | LIMITATION #9. THIS LIMITATION DOESN'T ALLOW NAIL |
| | ENHANCEMENT. SEE GENERAL LIMITATION #9 ON LAST PAGE OF |
| | NOA. |
| | |
| | NOTE: ENGINEER NEEDS TO REVISE RAS 117 CALCULATIONS. |
| | SEE COMMENT ABOVE. |
| | AND NEEDS TO REFERENCE THE SPECIFIC FASTENING OPTION |
| | FROM NOA 18-0919.12. |
| | |
| | ORIGINAL COMMENT: |
| | 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. |
| | |
| | RESPONSE: |
| | COORDINATE ALL PRODUCT APPROVALS WITH CONTRACTOR. SEE |
| | COMMENT 12(A) ABOVE. |
| | |
| | |
| | 14-OK. |
| | 15-OK. |
| | 16-OK. |
| | 17-OK. |
| | |
| | WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| | ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| | HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| | REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | |
| | PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY |
| | QUESTIONS REGARDING THESE COMMENTS, |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | DEVELOPMENT SERVICES DEPARTMENT |
| | BUILDING DIVISION |
| | (561)805-6712 |
| | [email protected] |
| | |
| | |
| | |