| Plan Review Notes For Permit 22031580 |
| Permit Number |
22031580 |
|
| Review Stop |
R |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-11-16 14:26:04 | ROOFING REVIEW | | | | | | ORIGINAL COMMENT: | | | 1- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC | | | 61G20-3.001 FOR | | | (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED | | | SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW | | | PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL | | | PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL): | | | | | | A) OK. | | | B) OK. | | | | | | C)FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE | | | DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL. | | | NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN | | | PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED | | | RAS 117 CALCULATIONS ARE REQUIRED. | | | | | | RESPONSE: | | | NOA 18-0919.12 DOESN'T SPECIFY WHICH APPROVED ASSEMBLY | | | IS GOING TO BE INSTALLED AND NEED TO PROVIDE SIGNED AND | | | SEALED RAS 117 CALCULATIONS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA. | | | NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CANNOT BE | | | USED. SEE GENERAL LIMITATION #9 ON LAST PAGE OF NOA. | | | | | | 2- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING | | | (NOT SIGNING AND SEALING) ABOVE PRODUCT APPROVALS AS | | | REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | BUILDING DIVISION | | | (561)805-6712 | | | [email protected] | | | |
|