Plan Review Notes
Plan Review Notes For Permit 22031580
Permit Number 22031580
Review Stop B
Sequence Number 1
Notes
Date Text
2022-07-22 17:12:16RESIDENTIAL (R3)ALTERATION BUILDING REVIEW COMMENTS
 CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS.
 PERMIT #22031580 849 ARDMORE RD
  
 NOTE:
 LEVEL 3 ALTERATION. SEC. 604 FBC-EXISTING BUILDING.
 SEC. 901.2 FBC-EXISTING BUILDING. SEC. 801.3
 FBC-EXISTING BUILDING. ALL NEW CONSTRUCTION ELEMENTS,
 COMPONENTS, SYSTEMS, AND SPACES SHALL COMPLY WITH THE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE.
  
 1- DRAWINGS WERE NOT SIGNED AND SEALED BY THE ARCHITECT
 AND ENGINEERS OF RECORD. ALL DRAWINGS NEED TO BE SIGNED
 AND SEALED AS REQUIRED BY CHAPTER 481 F.S. AND CHAPTER
 471 F.S. WHEN SUBMITTING DRAWINGS/DOCUMENTS FOR PUBLIC
 RECORDS.
 NOTE: SUBMIT DRAWINGS ELECTRONICALLY WITH VERIFIABLE
 DIGITAL SIGNATURE
  
 2- ALL PLANS UPLOADED TO PROJECTDOX FOR REVIEW ARE NOT
 LEGIBLE. NEED TO UPLOAD LEGIBLE DRAWINGS. SEC.
 107.2.1.3 CITY AMENDMENTS.
  
 3- BASED ON PLANS SUBMITTED, THIS IS ALTERATION LEVEL 3
 NOT LEVEL 2. ARCHITECT TO REVISE DESCRIPTION OF WORK ON
 SHEET G001. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE.
 SEC. 604 FBC-EXISTING BUILDING.
  
 4- REFLECTED CEILING PLAN ON SHEET A103 SHOWS PROPOSED
 BEDROOM #1 WITH A CEILING HEIGHT OF 6'8". THIS ROOM
 DOESN'T COMPLY WITH THE MINIMUM CEILING HEIGHT OF 7'-0"
 REQUIRED FOR HABITABLE ROOMS. THEREFORE, THIS ROOM CAN
 NOT BE USED AS A HABITABLE ROOM. SEC. R305.1
 FBC-RESIDENTIAL.
  
 5- NONE OF THE WINDOWS OF PROPOSED BEDROOM #1 COMPLY
 WITH THE BEDROOMS EMERGENCY ESCAPE SEC. R310.2.1
 FBC-RESIDENTIAL (NOTE: COORDINATE WITH ITEM #4 ABOVE).
 ALSO, SPECIFY TYPE AND SIZE OF EXISTING WINDOWS TO BE
 REPLACED ON PROPOSED BEDROOM #2 AND TYPE AND SIZE OF
 PROPOSED WINDOWS TO BE INSTALLED TO VERIFY COMPLIANCE
 WITH EGRESS REQUIREMENTS. SEC. 702.5 FBC-EXISTING
 BUILDING.
  
 6- SHEET S1: SPECIFY PROTECTION AGAINST WOOD DECAY FOR
 THE FLOOR JOISTS OF THE COVERED DECK AS REQUIRED BY
 SEC. R37 FBC-RESIDENTIAL.
  
 7- SHEET S3:
 A)REVISE "PROJECT SPECIFIC CODES USED", GRAVITY LOADING
 AND WIND LOADING. . CURRENT CODE IS THE 2020
 FBC-RESIDENTIAL NOT 2017. REVISE ALL THE INFORMATION
 ACCORDINGLY, INCLUDING CURRENT ASCE.
 SEC. 553 FLORIDA STATUTES.
  
 B)COMPONENTS AND CLADDING DESIGN PRESSURES ARE TOO LOW
 BASED ON SPECIFIED BUILDING EXPOSURE AND HEIGHT, DOORS
 AND WINDOWS ARE LOW. REVISE AS REQUIRED OR PROVIDE
 ACTUAL CALCULATIONS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 8- DETAIL 15/S2: WIND PRESSURES ARE TOO LOW BASED ON
 SPECIFIED BUILDING EXPOSURE AND HEIGHT. REVISE AS
 REQUIRED OR PROVIDE ACTUAL CALCULATIONS.
 SEC. R301.2.1 FBC-RESIDENTIAL.
  
 9- SPECIFY ROOF SHEATHING NAILING SPECIFICATIONS
 SHOWING COMPLIANCE WITH NEW 2020 FBC-RESIDENTIAL
 SPECIFICATIONS. SPECIFY NAIL TYPE, SIZE AND SPACING.
 NEED TO USE RING SHANK NAILS.
 SEC. R803.2.3.1 AND TABLE R803.2.3.1 FBC-RESIDENTIAL.
 NOTE: COORDINATE WITH SPECIFICATIONS SHOWN ON EXTERIOR
 ELEVATIONS SHEET A201, A202, A203 AND SECTION A ON
 SHEETS A301 TO AVOID CONFLICTS.
  
 10- WALL SECTIONS: NEED TO SPECIFY TWO WATER RESISTIVE
 BARRIERS WHEN STUCCO IS APPLIED TO WOOD AS REQUIRED BY
 SEC. R703.7.3 FBC-RESIDENTIAL.
  
 11- ROOFING UNDERLAYMENT
 PROVIDE SPECIFICATIONS SHOWING HOW COMPLYING WITH THE
 NEW 2020 CODE REQUIREMENT FOR ROOFING UNDERLAYMENT.
 SEC. R905.1.1.1 FBC-RESIDENTIAL.
 NOTE: CLEARLY SPECIFY WHICH METHOD OF SEC. R905.1.1.1
 FBC-RESIDENTIAL IS GOING TO BE USED. AND PROVIDE
 PRODUCT APPROVAL AS REQUIRED BY F.A.C. 61G20-3.001
  
 12- PROVIDE PRODUCT APPROVAL AS REQUIRED BY FAC
 61G20-3.001 FOR
 (NOTE: THIS MAY BE SUBMITTED LATER AS A DEFERRED
 SUBMITTAL. PROVIDE COMPLETE INFORMATION FOR REVIEW
 PRIOR TO INSTALLATION TO AVOID CONFLICTS/DELAYS. ALL
 PRODUCT APPROVALS NEED TO BE APPROVED IN WRITING BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL):
  
 A)INSWING ENTRY DOOR AS SHOWN ON PLANS.
 B)FRENCH DOORS.
 C)SINGLE HUNG WINDOWS.
 D)FIXED WINDOWS AS SPECIFIED ON WINDOW SCHEDULE. (NOTE:
 CLARIFY WHY ELEVATIONS DON'T SHOW FIXED WINDOWS).
 E)WINDOW MULLIONS (NOTE: NEED TO SPECIFY MULLION SIZE
 TO VERIFY PRESSURES. SEC. R301.2.1 FBC-RESIDENTIAL).
 F)ROOF SHINGLES.
 G)ROOFING UNDERLAYMENT SPECIFIED ON PLANS.
 H) FLAT ROOF. AND, CLEARLY MARK WHICH APPROVED ASSEMBLY
 IS GOING TO BE INSTALLED TO VERIFY COMPLIANCE WITH THE
 DESIGN PRESSURES OF SEC. R301.1 FBC-RESIDENTIAL.
 NOTE: IF THE SELECTED ASSEMBLY DOESN'T MEET THE DESIGN
 PRESSURES FOR ALL ROOF ZONES, THEN SIGNED AND SEALED
 RAS 117 CALCULATIONS ARE REQUIRED.
  
 13- DESIGNER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 107.3.4.1 CITY AMENDMENTS.
  
 14- HANDRAILS AND HANDRAILS: DESIGNER OF RECORD NEEDS
 TO PROVIDE THE DETAILS AND SPECIFICATIONS FOR THE
 CONSTRUCTION OF THE HANDRAILS AND GUARDRAILS AS
 REQUIRED BY TABLE R301.5, SEC. R311.7.8 AND SEC. R312.1
 FBC-RESIDENTIAL.
 NOTE: SUBSEQUENT SHOP DRAWINGS ARE TO CONFIRM THAT
 DESIGN DETAILS AND SPECIFICATIONS ARE MET.
  
 15-REVISE WINDOWS AND DOORS STRUCTURAL BUCK DETAILS
 SHOWN ON SHEET A501.
 STRUCTURAL BUCK NEEDS TO PROVIDE FULL SUPPORT TO THE
 DOOR/WINDOW FRAME AND NEED TO EXTEND BEYOND THE
 INTERIOR FACE OF THE WINDOW OR DOOR FRAME AS REQUIRED
 BY SEC. R609.7.2.1 FBC-RESIDENTIAL. ALSO, BEVELED BUCKS
 ARE NOT ALLOWED ANYMORE.
  
 16- VALUATION WAS REVISED TO REFLECT VALUE STATED ON
 THE COPY OF THE CONTRACT SUBMITTED ($172,868.75).
 DEDUCTED THE PERMIT FEE OF $6,800 FROM CONTRACT VALUE.
 TOTAL VALUE USED $166,068). THE PERMIT FEE BALANCE IS
 $3503.81.
 SEC. 109.3 CITY AMENDMENTS.
  
 WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE
 ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND
 HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE
 REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 PLEASE FEEL FREE TO CONTACT ME IF YOU HAVE ANY
 QUESTIONS REGARDING THESE COMMENTS,
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 BUILDING DIVISION
 (561)805-6712