2022-04-15 15:52:011ST REVIEW FMC
 PERMIT: 22031507
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REVISE THE VALUE OF WORK ON THE REVISION
 REQUEST FORM AS THIS WORK WAS NOT INCLUDED UNDER THE
 MAIN PERMIT.
  
 2) THE RETURN AIR SHALL NOT BE FROM A CLOSET.
  
 FRC M1602.2 RETURN AIR OPENINGS. RETURN AIR OPENINGS
 FOR HEATING, VENTILATION AND AIR CONDITIONING SYSTEMS
 SHALL COMPLY WITH ALL OF THE FOLLOWING: 4. RETURN AIR
 SHALL NOT BE TAKEN FROM A CLOSET, BATHROOM,
 TOILET ROOM, KITCHEN, GARAGE, MECHANICAL ROOM, BOILER
 ROOM, FURNACE ROOM OR UNCONDITIONED ATTIC.
  
 3) SHOW THE ANCHORAGE DETAIL OF THE OUTDOOR CONDENSING
 UNIT.
 M1307.2 ANCHORAGE OF APPLIANCES. APPLIANCES DESIGNED TO
 BE FIXED IN POSITION SHALL BE FASTENED OR ANCHORED IN
 AN APPROVED MANNER. IN SEISMIC DESIGN CATEGORIES D0, D1
 AND D2, AND IN TOWNHOUSES IN SEISMIC DESIGN CATEGORY C,
 WATER HEATERS AND THERMAL STORAGE UNITS SHALL BE
 ANCHORED OR STRAPPED TO RESIST HORIZONTAL DISPLACEMENT
 CAUSED BY EARTHQUAKE MOTION IN ACCORDANCE WITH ONE OF
 THE FOLLOWING:
 1. ANCHORAGE AND STRAPPING SHALL BE DESIGNED TO RESIST
 A HORIZONTAL FORCE EQUAL TO ONE-THIRD OF THE OPERATING
 WEIGHT OF THE WATER HEATER STORAGE TANK, ACTING IN ANY
 HORIZONTAL DIRECTION. STRAPPING SHALL BE AT POINTS
 WITHIN THE UPPER ONE-THIRD AND LOVER ONE-THIRD OF THE
 APPLIANCE?S VERTICAL DIMENSIONS. AT THE LOWER POINT,
 THE STRAPPING SHALL MAINTAIN A MINIMUM DISTANCE OF 4
 INCHES (102 MM) ABOVE THE CONTROLS.
 2. THE ANCHORAGE STRAPPING SHALL BE IN ACCORDANCE WITH
 THE APPLIANCE MANUFACTURER?S RECOMMENDATIONS.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  