| Plan Review Notes For Permit 22031501 |
| Permit Number |
22031501 |
|
| Review Stop |
R |
| Sequence Number |
8 |
|
| Notes |
| Date |
Text |
| 2022-12-07 11:58:18 | ROOF SYSTEM FOR THE ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK | | | (NOA 20-0723.29) - PLEASE CIRCLE THE ROOFING SYSTEM TO | | | BE USED IN THE ROOFING PRODUCT APPROVAL THAT MEETS THE | | | REQUIRED PRESSURES PER FBC TABLE R301.2(2) - ROOFING | | | SYSTEM TO BE USED ON THE PROVIDED PRODUCT APPROVAL MAY | | | REQUIRE ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS | | | FROM AN ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND | | | 3 WHICH REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM | | | SHOWN ON THE PRODUCT APPROVAL - SEE GENERAL LIMITATION | | | NOTE NUMBER 7 ON THE PRODUCT APPROVAL. (WORST CASE ZONE | | | 3 WILL NEED TO MEET (-73.30 ) | | | | | | 2) ROOFING SYSTEM PRODUCT APPROVALS MAY BE DEFERRED | | | SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE | | | CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1 | | | | | | | | | | | | | | | | | | | | | | | | |
|