2022-12-07 11:58:18ROOF SYSTEM FOR THE ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK
 (NOA 20-0723.29) - PLEASE CIRCLE THE ROOFING SYSTEM TO
 BE USED IN THE ROOFING PRODUCT APPROVAL THAT MEETS THE
 REQUIRED PRESSURES PER FBC TABLE R301.2(2) - ROOFING
 SYSTEM TO BE USED ON THE PROVIDED PRODUCT APPROVAL MAY
 REQUIRE ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS
 FROM AN ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND
 3 WHICH REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM
 SHOWN ON THE PRODUCT APPROVAL - SEE GENERAL LIMITATION
 NOTE NUMBER 7 ON THE PRODUCT APPROVAL. (WORST CASE ZONE
 3 WILL NEED TO MEET (-73.30 )
  
 2) ROOFING SYSTEM PRODUCT APPROVALS MAY BE DEFERRED
 SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON THE
 CONSTRUCTION DOCUMENTS - FBC WPB 107.3.4.1
  
  
  
  
  
  
  
  