| Plan Review Notes For Permit 22031501 |
| Permit Number |
22031501 |
|
| Review Stop |
B |
| Sequence Number |
6 |
|
| Notes |
| Date |
Text |
| 2022-11-04 15:59:09 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE FRONT PAGES FOR THE PROVIDED | | | FLORIDA PRODUCT APPROVALS. (FL17184 AND FL23359) | | | | | | 2) THE PROVIDED PRODUCT APPROVAL (NOA) 22-0617.06 FOR | | | THE ROOFING - THE CHOSEN PRODUCT APPROVAL SYSTEM TYPE | | | E-1 SHOWS A WIND DESIGN PRESSURE OF (-52.5) - FBC TABLE | | | R301.2(2) REQUIRES A ROOF WIND ZONE 3 TO HAVE A WIND | | | DESIGN PRESSURE OF (-73.30) WHICH IS HIGHER THAN THE | | | PRODUCT APPROVAL ALLOWS - THEREFORE SEE "GENERAL | | | LIMITATION NUMBER 7" IN THE PROVIDED PRODUCT APPROVAL - | | | WHICH SAYS TO PROVIDE SIGNED AND SEALED ADDITIONAL | | | ATTACHMENT ENGINEERING FROM AN ARCHITECT OR ENGINEER. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | |
|