Plan Review Notes
Plan Review Notes For Permit 22031501
Permit Number 22031501
Review Stop B
Sequence Number 4
Notes
Date Text
2022-09-19 11:18:00SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 3RD REVIEW
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE THE FRONT PAGES FOR THE PROVIDED
 FLORIDA PRODUCT APPROVALS. (FL17184 AND FL23359)
  
 2) PRODUCT APPROVAL (NOA) 17-0427.16 IS FOR A ROOF
 RECOVER - THE ROOFING SYSTEM IS NEW, IT WOULD NOT BE A
 RECOVER.
  
 3) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK -
 PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE
 ROOFING PRODUCT APPROVAL THAT MEETS THE REQUIRED
 PRESSURES PER FBC TABLE R301.2(2) - ROOFING SYSTEM TO
 BE USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE
 ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN
 ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH
 REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE
 PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7
 ON THE PRODUCT APPROVAL. (WORST CASE ZONE 3 WILL NEED
 TO MEET (-73.30 )
  
 4) PLEASE SHOW ROOF SHEATHING ATTACHMENT TYPE AND ON
 CENTER SPACING - FBC R803.2.3
  
 5) PLEASE SHOW THE EXTERIOR MASONRY WALL TO JOIST
 STRAPPING DESIGNATION AND ATTACHMENT. FBC 1604.8.1
  
  
  
  
  
  
  
  