2022-07-11 14:39:38PLEASE ADDRESS 1ST CYCLE COMMENTS BELOW.
  
  
  
 1ST REVIEW FMC
 PERMIT: 22031501
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE MECHANICAL SCOPE OF WORK INDICATES THAT YOU ARE
 ADDING A DUCT FROM THE AHU TO THE NEWLY ENCLOSED FAMILY
 ROOM. SHEET A 102 LISTS THE HEATING AND COOLING
 EQUIPMENT. IS THIS GOING TO BE A NEW MECHANICAL SYSTEM?
 WE WILL NEED FOR THE DESIGNER TO PROVIDE ENERGY
 CALCULATIONS FOR THIS NEW FAMILY ROOM AS WELL AS THE
 EQUIPMENT SIZING CALCULATIONS FOR THE MECHANICAL
 SYSTEM. FBC 107.2.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  