| Plan Review Notes For Permit 22031501 |
| Permit Number |
22031501 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2022-07-19 13:25:08 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE THE FRONT PAGES FOR THE PROVIDED | | | FLORIDA PRODUCT APPROVALS. (FL17184 AND FL23359) | | | | | | 2) IF PRODUCT APPROVALS ARE NOT LISTED ON THE DRAWINGS | | | BY THE PERMIT NUMBER THEY NEED TO BE REVIEWED AND | | | MARKED APPROVED BY THE ARCHITECT OF RECORD FBC WPB | | | 107.3.4 | | | | | | 3) IN THE PRODUCT APPROVAL PROVIDED FOR THE FLAT DECK - | | | PLEASE CIRCLE THE ROOFING SYSTEM TO BE USED IN THE | | | ROOFING PRODUCT APPROVAL THAT MEETS THE REQUIRED | | | PRESSURES PER FBC TABLE R301.2(2) - ROOFING SYSTEM TO | | | BE USED ON THE PROVIDED PRODUCT APPROVAL MAY REQUIRE | | | ADDITIONAL SIGNED AND SEALED ATTACHMENT DETAILS FROM AN | | | ARCHITECT OR ENGINEER FOR ROOF WIND ZONES 2 AND 3 WHICH | | | REQUIRE A HIGHER PRESSURE THAN THE MAXIMUM SHOWN ON THE | | | PRODUCT APPROVAL - SEE GENERAL LIMITATION NOTE NUMBER 7 | | | ON THE PRODUCT APPROVAL. (WORST CASE ZONE 3 WILL NEED | | | TO MEET (-73.30 ) | | | | | | 4) PLEASE SHOW ROOF SHEATHING ATTACHMENT TYPE AND ON | | | CENTER SPACING - FBC R803.2.3 | | | | | | 5) PLEASE SHOW THE EXTERIOR MASONRY WALL TO JOIST | | | STRAPPING DESIGNATION AND ATTACHMENT. FBC 1604.8.1 | | | | | | | | | | | | | | | | | | | | | | | | |
|