| Notes |
| Date |
Text |
| 2022-05-25 15:23:47 | SFR ADDITION | | | REVIEWED BY ROGER MCPHERSON | | | 561-805-6716 | | | [email protected] | | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | | AMENDMENT | | | | | | CORRECTIONS NEEDED - | | | | | | 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE | | | INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE | | | PRODUCT APPROVALS FOR THE EXTERIOR DOORS, WINDOWS AND | | | ROOFING SYSTEMS - AS LISTED ON THE DRAWINGS. | | | | | | 2) DRAWING A 101 SHOWS THE CODE VERSION USED IS 2017 | | | FBC - SHOULD BE 2020 FBC | | | | | | 3) PLEASE SHOW THE REQUIRED TERMITE PROTECTION PER FBC | | | R318.1 | | | | | | 4) R 30 INSULATION SHOWN BETWEEN 2 X 8 FRAMING DOES NOT | | | ALLOW FOR THE 1 INCH CLEARANCE FOR VENTILATION PER - | | | FBC R806.3 VENT AND INSULATION CLEARANCE. | | | WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING, | | | BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW | | | OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE | | | PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING | | | AND AT THE LOCATION OF THE VENT. | | | | | | 5) PLEASE SHOW THE ROOF SLOPE PER FBC R905.9.1 | | | | | | 6) PLEASE PROVIDE A SURVEY. | | | | | | |
|