Plan Review Notes
Plan Review Notes For Permit 22031501
Permit Number 22031501
Review Stop B
Sequence Number 1
Notes
Date Text
2022-05-25 15:23:47SFR ADDITION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR DOORS, WINDOWS AND
 ROOFING SYSTEMS - AS LISTED ON THE DRAWINGS.
  
 2) DRAWING A 101 SHOWS THE CODE VERSION USED IS 2017
 FBC - SHOULD BE 2020 FBC
  
 3) PLEASE SHOW THE REQUIRED TERMITE PROTECTION PER FBC
 R318.1
  
 4) R 30 INSULATION SHOWN BETWEEN 2 X 8 FRAMING DOES NOT
 ALLOW FOR THE 1 INCH CLEARANCE FOR VENTILATION PER -
 FBC R806.3 VENT AND INSULATION CLEARANCE.
 WHERE EAVE OR CORNICE VENTS ARE INSTALLED, BLOCKING,
 BRIDGING AND INSULATION SHALL NOT BLOCK THE FREE FLOW
 OF AIR. NOT LESS THAN A 1-INCH (25 MM) SPACE SHALL BE
 PROVIDED BETWEEN THE INSULATION AND THE ROOF SHEATHING
 AND AT THE LOCATION OF THE VENT.
  
 5) PLEASE SHOW THE ROOF SLOPE PER FBC R905.9.1
  
 6) PLEASE PROVIDE A SURVEY.
  
  