| 2022-05-09 13:39:12 | ELECTRIC REVIEW FAILED | | | 1) DIAGRAM INCORRECTLY DETAILS 1/0 SERVICE CONDUCTORS | | | FROM METER TO DISCONNECT TO PANEL A . PLEASE CORRECT TO | | | CORRECT SIZED 2/0 CU CONDUCTORS AS PER NEC NEC 310.15 | | | (B)(7)(2) | | | 2) RISER DIAGRAM DOES NOT DETAIL OVERCURRENT PROTECTION | | | FEEDING PANEL B. PLEASE DETAIL OVERCURRENT PROTECTION | | | TO CORRECTLY PROTECT 1/0 FEEDER CONDUCTORS FROM PANEL A | | | TO PANEL B. NEC 240.4 | | | 3) IT APPEARS PANEL A IS LOCATED IN A CLOSET. PLEASE | | | DETAIL HOW THIS IS CODE COMPLIANT WITH NEC 240.24 (D) | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | | | | |
|