| 2022-04-20 16:04:54 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| | MARSHAL, WITH THE FOLLOWING COMMENTS: |
| | |
| | THE RESUBMITTED DOCUEMNTS DO NOT SPECIFICALLY PROVIDE |
| | ANY CLARIFYING INFORMATION REGARDING THE PREVIOUS FIRE |
| | COMMENTS; |
| | |
| | PLEASE PROVIDE DETAILED INFORMATION/DOCUMENTION TO THE |
| | NOTED COMMENTS POSTED BELOW. |
| | |
| | PLEASE INCLUDE BUILDING PLAN VIEWS/CALLOUTS SHOWING |
| | APPLICABLE LOCATIONS WITH DIMENSIONS AS APPLICABLE. |
| | |
| | |
| | 1) THERE IS AN INDICATION OF A HOOD, HOWEVER, THERE IS |
| | NO INDICATION OF WHAT TYPE OF HOOD IT IS. |
| | |
| | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE HOOD TYPE |
| | PER NFPA 96 . |
| | |
| | |
| | 1A) THERE IS NO INDICATION OF A PROPOSED FIRE |
| | SUPRESSION SYSTEM ASSOCIATED WITH THIS HOOD. |
| | |
| | PLEASE PROVIDE A NOTE FOR THE FIRE SUPPRESSION SYSTEM |
| | IF REQUIRED FOR THE HOOD TYPE PER # 1 ABOVE. |
| | |
| | |
| | 2) THERE ARE PLAN SHEETS FOR THE 5TH FL SKY LOUNGE ABD |
| | 1ST FL LAUNDRY. |
| | |
| | FOR CLARIFICATION PURPOSES, WHY ARE THESE PLAN SHEETS |
| | SUBMITTED FOR? |
| | |
| | |
| | |
| | 3) THERE ARE NO INDICATIONS OF THE EXHAUST VENTING |
| | DETAILS, VENT TERMINATION AND ANY MAKEUP AIR EQUIPMENT. |
| | |
| | THESE DETAILS AND DIMENSIONS ARE REQUIRED TO MEET THE |
| | REQUIRMENTS OF NFPA 96. |
| | |
| | PLEASE PROVIDE DETAILS. |
| | |
| | |
| | |
| | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| | ABOVE. |
| | |
| | |
| | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| | RE-SUBMITTAL OF THE ABOVE. |
| | |
| | |
| | PETER LEDUC |
| | FIRE MARSHAL |