| 2022-12-20 06:40:29 | 1ST AUDIT FMC |
| | PERMIT: 22031422 |
| | |
| | CODES IN EFFECT: 2020 |
| | |
| | FBC- FLORIDA BUILDING CODE |
| | FMC- FLORIDA MECHANICAL CODE |
| | FEC- FLORIDA ENERGY CONSERVATION |
| | FGC- FLORIDA FUEL GAS |
| | FEX- FLORIDA EXISTING BUILDING CODE |
| | FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| | F.S.- FLORIDA STATUTES |
| | FAC- FLORIDA ACCESSIBILITY CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| | |
| | AUDIT RESULTS: DENIED. |
| | |
| | 1) THE PERMIT APPLICATION DOES NOT HAVE ANY WORK |
| | DESCRIPTION. PROVIDE A DESCRIPTION OF WORK I.E. IF IT |
| | IS FOR ONE PIZZA OVEN PLEASE STATE THIS. FBC 107.3.5 |
| | |
| | 2) THE VALUE OF THIS PROJECT SHOULD INCLUDE THE |
| | EQUIPMENT AND LABOR. THE $2,500.00 VALUE APPEARS TO BE |
| | LOW FOR THIS WORK. PROVIDE AN ACCURATE VALUE FOR THIS |
| | PROJECT. |
| | |
| | 3) PROVIDE THE HOOD TYPE ON THE SPECIFICATIONS I.E. |
| | TYPE I. FMC 507.2 |
| | |
| | 4) PROVIDE GREASE DUCT DRAWINGS; THESE SHOULD INCLUDE |
| | THE DUCT MATERIAL, SIZE, DISTANCE, CLEANOUTS, SLOPE, |
| | CLEARANCES TO COMBUSTIBLES, TERMINATION LOCATION WITH |
| | TERMINATION CLEARANCES FROM PROPERTY LINES AND ABOVE |
| | GRADE. FBC 107.3.5 |
| | |
| | |
| | 5) PLEASE SHOW THE AIR VELOCITY FOR THIS TYPE 1 GREASE |
| | DUCT. FMC 506.3.4 |
| | |
| | 6) SHOW HOW THE MAKE-UP AIR WILL BE INTRODUCED FOR THIS |
| | HOOD. THE FACILITY AIR BALANCE SCHEDULE INDICATES AIR |
| | TRANSFER OF 950 CFM FROM AN ADJACENT SPACE. SPECIFY |
| | THIS ADJACENT SPACE AND SHOW THE CALCULATIONS FOR THIS |
| | TRANSFER OF AIR. FBC 107.3.5 |
| | |
| | 7) PROVIDE THE COMBUSTION AIR CALCULATIONS. |
| | FMC 701.1 SCOPE. SOLID FUEL-BURNING APPLIANCES SHALL BE |
| | PROVIDED WITH COMBUSTION AIR IN ACCORDANCE WITH THE |
| | APPLIANCE MANUFACTURER???S INSTALLATION INSTRUCTIONS. |
| | |
| | 8) PROVIDE THE SPECIFICATIONS FOR THE PIZZA OVEN. |
| | PLEASE SHOW THAT THIS PIZZA OVEN IS LISTED AND LABELED |
| | IN ACCORDANCE WITH UL 2162. FMC 917.1 SOLID-FUEL-FIRED |
| | OVENS SHALL BE LISTED AND LABELED IN ACCORDANCE WITH UL |
| | 2162. |
| | |
| | 9) PROVIDE INFORMATION ON THE IN-LINE FAN KEF-4, ALSO |
| | INCLUDE A DETAIL DRAWING OF THE 2-HOUR RATING FOR THE |
| | ENCLOSURE AND THE VENTILATION REQUIREMENTS OF THE |
| | MANUFACTURER. FMC 506.5.1.2 |
| | |
| | 10) PROVIDE INFORMATION ON THE IN-LINE FAN KEF-4, ALSO |
| | INCLUDE A DETAIL DRAWING OF THE 2-HOUR RATING FOR THE |
| | ENCLOSURE AND THE VENTILATION REQUIREMENTS OF THE |
| | MANUFACTURER. FMC 506.5.1.2 |
| | |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM. |
| | |