Plan Review Notes
Plan Review Notes For Permit 22031422
Permit Number 22031422
Review Stop M
Sequence Number 1
Notes
Date Text
2022-12-20 06:40:291ST AUDIT FMC
 PERMIT: 22031422
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 AUDIT RESULTS: DENIED.
  
 1) THE PERMIT APPLICATION DOES NOT HAVE ANY WORK
 DESCRIPTION. PROVIDE A DESCRIPTION OF WORK I.E. IF IT
 IS FOR ONE PIZZA OVEN PLEASE STATE THIS. FBC 107.3.5
  
 2) THE VALUE OF THIS PROJECT SHOULD INCLUDE THE
 EQUIPMENT AND LABOR. THE $2,500.00 VALUE APPEARS TO BE
 LOW FOR THIS WORK. PROVIDE AN ACCURATE VALUE FOR THIS
 PROJECT.
  
 3) PROVIDE THE HOOD TYPE ON THE SPECIFICATIONS I.E.
 TYPE I. FMC 507.2
  
 4) PROVIDE GREASE DUCT DRAWINGS; THESE SHOULD INCLUDE
 THE DUCT MATERIAL, SIZE, DISTANCE, CLEANOUTS, SLOPE,
 CLEARANCES TO COMBUSTIBLES, TERMINATION LOCATION WITH
 TERMINATION CLEARANCES FROM PROPERTY LINES AND ABOVE
 GRADE. FBC 107.3.5
  
  
 5) PLEASE SHOW THE AIR VELOCITY FOR THIS TYPE 1 GREASE
 DUCT. FMC 506.3.4
  
 6) SHOW HOW THE MAKE-UP AIR WILL BE INTRODUCED FOR THIS
 HOOD. THE FACILITY AIR BALANCE SCHEDULE INDICATES AIR
 TRANSFER OF 950 CFM FROM AN ADJACENT SPACE. SPECIFY
 THIS ADJACENT SPACE AND SHOW THE CALCULATIONS FOR THIS
 TRANSFER OF AIR. FBC 107.3.5
  
 7) PROVIDE THE COMBUSTION AIR CALCULATIONS.
 FMC 701.1 SCOPE. SOLID FUEL-BURNING APPLIANCES SHALL BE
 PROVIDED WITH COMBUSTION AIR IN ACCORDANCE WITH THE
 APPLIANCE MANUFACTURER???S INSTALLATION INSTRUCTIONS.
  
 8) PROVIDE THE SPECIFICATIONS FOR THE PIZZA OVEN.
 PLEASE SHOW THAT THIS PIZZA OVEN IS LISTED AND LABELED
 IN ACCORDANCE WITH UL 2162. FMC 917.1 SOLID-FUEL-FIRED
 OVENS SHALL BE LISTED AND LABELED IN ACCORDANCE WITH UL
 2162.
  
 9) PROVIDE INFORMATION ON THE IN-LINE FAN KEF-4, ALSO
 INCLUDE A DETAIL DRAWING OF THE 2-HOUR RATING FOR THE
 ENCLOSURE AND THE VENTILATION REQUIREMENTS OF THE
 MANUFACTURER. FMC 506.5.1.2
  
 10) PROVIDE INFORMATION ON THE IN-LINE FAN KEF-4, ALSO
 INCLUDE A DETAIL DRAWING OF THE 2-HOUR RATING FOR THE
 ENCLOSURE AND THE VENTILATION REQUIREMENTS OF THE
 MANUFACTURER. FMC 506.5.1.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  