| Plan Review Notes For Permit 22031422 |
| Permit Number |
22031422 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2022-04-18 12:45:32 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | | | 1) THERE IS AN INDICATION OF A HOOD, HOWEVER, THERE IS | | | NO INDICATION OF WHAT TYPE OF HOOD IT IS. | | | | | | FOR THE OFFICIAL RECORD, PLEASE PROVIDE THE HOOD TYPE | | | PER NFPA 96 . | | | | | | | | | 1A) THERE IS NO INDICATION OF A PROPOSED FIRE | | | SUPRESSION SYSTEM ASSOCIATED WITH THIS HOOD. | | | | | | PLEASE PROVIDE A NOTE FOR THE FIRE SUPPRESSION SYSTEM | | | IF REQUIRED FOR THE HOOD TYPE PER # 1 ABOVE. | | | | | | | | | 2) THERE ARE PLAN SHEETS FOR THE 5TH FL SKY LOUNGE ABD | | | 1ST FL LAUNDRY. | | | | | | FOR CLARIFICATION PURPOSES, WHY ARE THESE PLAN SHEETS | | | SUBMITTED FOR? | | | | | | | | | | | | 3) THERE ARE NO INDICATIONS OF THE EXHAUST VENTING | | | DETAILS, VENT TERMINATION AND ANY MAKEUP AIR EQUIPMENT. | | | | | | THESE DETAILS AND DIMENSIONS ARE REQUIRED TO MEET THE | | | REQUIRMENTS OF NFPA 96. | | | | | | PLEASE PROVIDE DETAILS. | | | | | | | | | | | | 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | | ABOVE. | | | | | | | | | 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | | RE-SUBMITTAL OF THE ABOVE. | | | | | | | | | PETER LEDUC | | | FIRE MARSHAL | | | 561-804-4709 | | | [email protected] | | | |
|