| 2022-04-28 13:31:16 | ELECTRIC REVIEW FAILED | | | 1) RISER DIGRAM DETAILS 2/0 FEEDERS TO 200 INTERIOUR | | | PANEL. THIS FEEDER DOES NOT CARRY THE ENTIRE LOAD OF | | | THE DWELLING AS REQUIRED FOR DERATING AS PER NEC 310.15 | | | (B)(7)(2).PLEASE SIZE FEEDER CONDUCTORS PER | | | 310.15(B)(16) AS REQUIRED. | | | 2) PLEASE DETAIL THE GENERATOR AND WIRING AS BEING | | | INSTALLED UNDER A SEPERATE PERMIT AS PER WEST PALM | | | BEACH POLICY. A NOTE WILL SUFFICE | | | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | | RESUBMITTAL FORM. | | | | | | CODES IN EFFECT: | | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | | BUILDING CODE 2020 7TH ED. | | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | | 7TH EDITION | | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | | 7TH EDITION | | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | | FS = FLORIDA STATUTES | | | | | | V/R, | | | | | | MICHAEL PETERSON | | | ELECTRICAL PLANS EXAMINER | | | [email protected] | | | 561-805-6746 | | | |
|