Plan Review Notes
Plan Review Notes For Permit 22031400
Permit Number 22031400
Review Stop P
Sequence Number 1
Notes
Date Text
2022-04-27 11:51:421ST REVIEW FBC-2020 PLUMBING
 PERMIT-22031400
 4/27/2022
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC B- FLORIDA BUILDING CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET A119: THE NEW SHOWER AND LAVATORY SHALL BE
 ACCESSIBLE IN COMPLIANCE WITH SECS. 213.3, 213.3.4,
 213.3.6- FBC ACC. PROVIDE ENLARGED DRAWINGS AND DETAILS
 INCLUDING-
  
 A) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 LAVATORY- SEC. 606.2.
 B) KNEE AND TOE CLEARANCES FOR THE LAVATORY- SEC.
 606.2.
 C) HEIGHT OF THE LAVATORY SINK RIM OR COUNTER SURFACE
 FROM THE FINISHED FLOOR- SEC. 606.3.
 D) WIDTH AND DEPTH DIMENSIONS OF THE SHOWER- SEC.
 608.2.2.
 D) CLEAR FLOOR SPACE DIAGRAM AND DIMENSIONS FOR THE
 SHOWER- SEC. 608.2.2.1 (SEE EXCEPTION FOR LAVATORY).
 E) LOCATIONS, LENGTHS, AND MOUNTING HEIGHTS OF GRAB
 BARS FOR THE ACCESSIBLE SHOWER- SEC. 608.3 AND 608.3.2.
 F) LOCATION OF CONTROL, FAUCET, AND SHOWER SPRAY IN THE
 SHOWER- SEC. 608.5.2.
 G) SHOWER SPRAY UNIT SPECIFICATIONS PER SEC. 608.6.
 H) LOCATION OF ACCESSIBLE SHOWER SEAT (IF PROVIDED)-
 SECS. 610.3 & 610.3.2.
  
 2) A119: DETAIL 7 INDICATES THE SHOWER THRESHOLD WILL
 NOT BE IN COMPLIANCE WITH SEC. 608.7 FBC ACC WHICH
 LIMITS THRESHOLD HEIGHT TO 1/2-INCH MAXIMUM, AND THE
 THRESHOLD SHALL BE BEVELED, ROUNDED, OR VERTICAL.
  
 3) A119: CLARIFY HOW THE MINIMUM NUMBER OF WATER CLOSET
 FIXTURES FOR FEMALE USE IS BEING MET WITH REMOVAL OF
 THE WATER CLOSET FROM THE WOMEN'S TOILET ROOM- TABLE
 403.1 FBC P.
  
 4) P0.1 & P1.1: INDICATE HOW TEMPERED WATER WILL BE
 DELIVERED FROM THE LAVATORY- SEC. 419.5 FBC P.
  
 5) P0.1 & P1.1: SHOW THE MEANS OF LIMITING THE HOT
 WATER TEMPERATURE DELIVERY AT THE SHOWER FAUCET PER
 SECS. 412.3 & 607.1.1 FBC P.
  
 6) P0.1 & P1.1: THE NEW SHOWER DRAIN PIPE PENETRATING
 THE SLAB WILL REQUIRE THE FLOOR TO BE X-RAYED TO IN
 ORDER TO LOCATE REINFORCING STEEL OR POST STRESSED
 FLOOR TENDONS. PLEASE PLACE A NOTE ON THE PLANS TO
 VERIFY COMPLIANCE WILL BE MET- SECTION 107.2.1 WPB.
  
 7) NEW DRAIN PIPE PENETRATIONS OF THE EXISTING SLAB
 WILL REQUIRE FIRESTOPPING TO SEAL THE ANNULAR SPACE
 AROUND THE PIPING. PROVIDE A UL TESTED AND APPROVED
 FIRESTOPPING ASSEMBLY DETAIL ON THE PLAN- SECTION 315.1
 FBC P AND SECTION 714.4.1.2 FBC B.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  