| 2022-04-04 14:10:24 | 1ST GAS REVIEW | | | | | | V7 FPC - 2020 FLORIDA PLUMBING CODE | | | V7 FGC - 2020 FLORIDA FUEL GAS | | | V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE | | | V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE | | | V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE | | | V7 FEC - 2020 FLORIDA ENERGY CONSERVATION | | | 2021 F.S. - 2021 FLORIDA STATUTES | | | 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE | | | 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE | | | FBC CHAPTER 1 | | | | | | THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED | | | BY RYAN BROWN WITH THE FOLLOWING COMMENTS. | | | | | | 1. V7 FRC G2415.8 - THE GAS PIPING RUNNING THROUGH | | | SOLID FLOORS SHALL EITHER COMPLY WITH G2415.8, OR ONE | | | OF THE METHODS WITH CONDUIT(SLEEVE) | | | G2415.8.1/G2415.8.2. YOU HAVE SHOWN THE SLEEVE METHOD | | | BUT BOTH ENDS OF THE CONDUIT ARE LOCATED IN | | | INACCESSIBLE LOCATIONS. | | | | | | 2, V7 FRC G2415.17.1 - THE USE OF PLASTIC PIPE (HDPE) | | | IS PROHIBITED INDOORS. IT SHALL NOT BE USED WITHIN ANY | | | BUILDING OR UNDER ANY SLAB. IT IS ALLOWED UNDER | | | WALKWAYS OUTDOORS AS LONG IT IS BURIED IN COMPLIANCE | | | WITH G2415.10, BUT THE SLEEVES MUST COMPLY WITH | | | G2415.8.1/G2415.8.2. | | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | | LETTER ADDRESSING EACH ITEM. | | | | | | | | | RYAN W. BROWN | | | CHIEF PLUMBING INSPECTOR | | | OFFICE: 561-805-6692 | | | CELL: 561-517-4293 | | | EMAIL: [email protected] | | | |
|