Plan Review Notes
Plan Review Notes For Permit 22031357
Permit Number 22031357
Review Stop G
Sequence Number 1
Notes
Date Text
2022-04-04 14:10:241ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. V7 FRC G2415.8 - THE GAS PIPING RUNNING THROUGH
 SOLID FLOORS SHALL EITHER COMPLY WITH G2415.8, OR ONE
 OF THE METHODS WITH CONDUIT(SLEEVE)
 G2415.8.1/G2415.8.2. YOU HAVE SHOWN THE SLEEVE METHOD
 BUT BOTH ENDS OF THE CONDUIT ARE LOCATED IN
 INACCESSIBLE LOCATIONS.
  
 2, V7 FRC G2415.17.1 - THE USE OF PLASTIC PIPE (HDPE)
 IS PROHIBITED INDOORS. IT SHALL NOT BE USED WITHIN ANY
 BUILDING OR UNDER ANY SLAB. IT IS ALLOWED UNDER
 WALKWAYS OUTDOORS AS LONG IT IS BURIED IN COMPLIANCE
 WITH G2415.10, BUT THE SLEEVES MUST COMPLY WITH
 G2415.8.1/G2415.8.2.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  